Low Voltage Leakage Locator

Send Inquiry
Low Voltage Leakage Locator
Details
Live leakage testing for 0.4kV without power cut
Flexible clamp + dual slave units, accurate segmented line positioning
Bluetooth APP waveform storage, traceable leakage current data
Category
Circuit Breaker Analyzer
Share to
Description

Product Introduction

 

MOEORW-WKL16 Low Voltage Leakage Locator is an online complete set of earth fault detection equipment applicable to 0.4kV low voltage power distribution system. It adopts characteristic current signal coupling injection technology, which can accurately locate line earth leakage fault points without power cut during equipment operation. The complete set consists of main tester, coupling signal clamp, 2 signal collection slave units, flexible large-aperture current clamp meter and full supporting accessories. Matched with exclusive Bluetooth mobile analysis APP, it integrates signal injection, on-site induction collection, data storage and waveform analysis functions. One set covers all working conditions of low voltage leakage inspection, suitable for leakage fault rush repair in power operation & maintenance, engineering overhaul, complete distribution

 

Product Parameter (specification)

 

Main Unit Specifications

Display Screen

10.1 inch, resolution 800*480

Power Supply Battery

9600mAh lithium battery, auto power-off protection when voltage below 10V

Charging Standard

DC 12.6V/2A

Total Power

2.2W, output signal amplitude ≤2V

Dimension

260mm×170mm×60mm, total weight 2Kg

Operation Buttons

Power Switch, Charging Port, Channel Select Key, Running Indicator Light

 

Coupling Clamp Specifications

Clamp Inner Diameter

Φ123mm, compatible with various thick transformer grounding wires

Operating Ambient Humidity

Relative Humidity <80%

Dimension & Weight

290mm172mm30mm, weight 1kg

 

Clamp-type Slave Unit (Slave 1) Specifications

Clamp Inner Diameter

Φ123mm, compatible with various thick transformer grounding wires

Operating Ambient Humidity

Relative Humidity <80%

Dimension & Weight

290mm172mm30mm, weight 1kg

 

Handheld Induction Slave Unit (Slave 2) Specifications

Communication

Bluetooth 2.4G, Bluetooth

Name

HC-08SC

Power Supply

9V 6F22 Square Battery Continuous

Working Time

3 hours, support F1/F2/F3/F4 4-channel switching & calibration

Signal Indication

3-level strength indicator (Green/Yellow/Red) + bar battery indicator

Dimension & Weight

408mm79mm42mm, weight 0.2Kg

Function

Close-range detection of hidden leakage points on utility poles, stay wires, trees and wall-through cables

 

Flexible Clamp Meter Specifications

Total Coil Length

628mm, Coil Inner Diameter Φ200mm, can wrap A/B/C/N four cables at the same time

Applicable Line

Low voltage distribution line below AC600V

Current Range

AC 0.00A~9999A, resolution 10mA

Measurement Accuracy

±2%rdg±3dgt (wire placed at coil center, standard test environment 23℃±2℃)

Storage Function

Single meter stores up to 99 groups of test data, support peak hold, data view & clear

Power Supply

9V square battery, auto power-off after 2 minutes idle

 

Product feature

 

1: Online Detection Without Power Cut, Maintenance Efficiency Increased by 80%

  • Product Feature: Non-contact signal injection via coupling clamp, no need to disconnect low voltage live wire & neutral wire, no power-cut report coordination with users;
  • Technical Support: Independent characteristic circulation isolated from power frequency loop, detection will not affect normal power consumption of residents and factories;
  • Customer Benefit: Traditional segmented power-cut inspection takes average 120 mins for single leakage fault, this instrument locks fault point within 20 mins on average, 3-5 fault rush repairs can be finished per day, greatly improving operation & construction efficiency.
     

2: Triple Detection System, Full Coverage of All Working Conditions Without Blind Spots

  • Product Feature: Flexible clamp for general leakage screening of transformer area + clamp slave unit for overhead main line inspection + handheld slave unit for hidden fault positioning, one set replaces 3 single-function testers;
  • Technical Support: Flexible coil collects zero-sequence leakage current of four lines synchronously, two slave units conduct long & short distance induction separately, 4-channel signals match main unit uniformly with synchronous & error-free data;
  • Customer Benefit: No need to purchase multiple testing instruments separately to reduce total procurement cost, compatible with all test scenarios including outdoor, indoor, high-altitude and underground cables.
     

3: Matched Intelligent Bluetooth Analysis APP, Fit for Digital Distribution Account Management

  • Product Feature: Connect two slave units simultaneously via mobile Bluetooth, free switch of 4 channels, real-time current value display by A/B/C/N phase, auto generate test waveform curves; support grouped data storage, history record query and data filing;
  • Technical Support: Real-time collection of characteristic current value, APP automatically compares current difference before and after fault, visually displays leakage attenuation curve;
  • Customer Benefit: Meet digital operation filing requirements of State Grid transformer stations, completely replace paper records, fit for bidding of smart power grid and modern property maintenance projects.
     

4: Universal Battery Power Supply Scheme, No Endurance Shortage for Outdoor Work

  • Product Feature: Main unit with large-capacity lithium battery for long endurance, two slave units and flexible clamp meter all adopt commercially available No.7 / 9V dry batteries;
  • Technical Support: Split independent power supply design, ordinary dry batteries can be purchased locally for replacement when no charging condition outdoors, no special supporting chargers required;
  • Customer Benefit: No need to carry multiple chargers for outdoor inspection, eliminate endurance worries for field rush repair, reduce after-sales consultation and complaints related to battery life.
     

5: Multiple Safety Protection Design, Comply with Power Operation Safety Standards

  • Product Feature: Whole machine insulation fits AC600V low voltage operation, signal only transmitted through coupling clamp, direct connection of main unit to live lines is strictly prohibited; operation not recommended on rainy days, auto power-off under low voltage, sealed insulated equipment without exposed metal parts; matched IP67 waterproof & shockproof protective case;
  • Technical Support: All equipment pass withstand voltage & insulation test before delivery, signal loop isolated from high voltage live loop to avoid electric shock risk; unauthorized disassembly will void official warranty;
  • Customer Benefit: Meet mandatory safety assessment standards of power supply stations and power engineering, full safety instructions can be directly used for safety qualification response in bidding.

 

Product Application

 

  • Urban & Rural 0.4kV Low Voltage Distribution Transformer Area: General leakage inspection at transformer main grounding point and area branch box, rapidly locate leakage partition;
  • Outdoor Overhead Power Lines: Inspection of leakage faults on high-altitude main lines, T-joint branch lines, road/tree crossing cables, solve frequent RCD tripping issues;
  • Residential Incoming Distribution Lines: Detection of neutral/live wire earth leakage of community households, hidden earth faults of indoor concealed wires;
  • Utility Pole Auxiliary Facilities: Detection of earth leakage caused by metal stay wires, pole grounding and damaged insulators;
  • Industrial & Mining Plant Power Distribution: Inspection of workshop low voltage cables, equipment shell earth leakage and distribution cabinet zero-sequence leakage;
  • Property Community Operation & Maintenance: Regular inspection of basement cables, wall-through pipelines and leakage caused by green trees touching wires;
  • Power Engineering Rush Repair & Third-party Distribution Testing Institutions: Rapid survey of mass fault points, leakage testing for project acceptance;
  • High & Low Voltage Complete Equipment Factory: Pre-inspection of hidden leakage hazards for complete distribution cabinets before delivery.

 

Standard Configuration

 

  • Low Voltage Leakage Locator Main Unit ×1
  • Coupling Signal Clamp ×1
  • Clamp-type Signal Slave Unit (Slave 1) ×1
  • Handheld Induction Slave Unit (Slave 2) ×1
  • 628mm Flexible Current Clamp Meter ×1
  • Special Lithium Battery Charger 12.6V/2A ×1
  • IP67 Shockproof & Waterproof Engineering Protective Case ×1
  • Supporting Leakage Locator Assistant APP

 

FAQ

 

Q: Are you a manufacturer or a trading company?

A: We are a direct manufacturer specializing in high-voltage testing equipment. We have our own R&D team and production facility, which allows us to offer factory-direct pricing and strict quality control.

Q: What is your warranty and after-sales policy?

A: All units come with a 12-month warranty. After the warranty expires, we provide lifetime technical support and paid maintenance services.

Q: Do you support English language interfaces?

A: Yes, our standard models feature English keyboards, software, and user manuals. If you require other languages, please contact us to check availability for customization.

 

Hot Tags: low voltage leakage locator, China low voltage leakage locator manufacturers, factory, Breaker Simulator, Circuit Breaker Analyzer CB Analyzer, circuit breaker tester, contact pressure gauge, contact pressure switch, Double Grounded Circuit Breaker Analyzer

Send Inquiry