Transformer Parameter Tester

Send Inquiry
Transformer Parameter Tester
Details
MOEORW-W4300 Transformer Parameter Tester accurately measures no-load/load parameters and 31st-order harmonics. It supports multi-dimensional auto-calibration, features simple wiring with correctness verification, offers convenient data storage and export, and adapts to complex operating conditions. This reliable professional equipment is essential for power testing applications.
Category
Transformer Load and No Load Loss Tester
Share to
Description

Transformer Parameter Tester

 

Product Introduction

 

    MOEORW-W4300 is a professional testing equipment designed for power operation and maintenance, scientific research experiments, and industrial and mining production scenarios. It can accurately complete the full-parameter detection of transformers under no-load and load conditions, and supports in-depth analysis of up to the 31st harmonic. The instrument is equipped with a multi-dimensional automatic calibration system, which simplifies the wiring process and has a built-in wiring correctness verification function. Data can be quickly stored, exported and printed on-site, and it can adapt to various complex on-site working conditions, making it the core testing tool in power test scenarios.

 

Product Parameter (specification)

 

1. Environmental Conditions

Temperature

-5°C to 40°C

Relative Humidity

<95% (at 25°C)

Altitude

<2500m

External Interference

No extreme vibration, no strong electromagnetic fields

Power Supply

220VAC ±15%, 50Hz to 60Hz

2. Measurement Range

Voltage

0 to 800V

Current

0 to 100 A

Frequency

45 Hz to 65 Hz

3. Test Accuracy

Voltage, Current

Class 0.1

Frequency

Measurement accuracy Class 0.2

Power

Measurement error < ±0.5% (CosΦ > 0.1), ±1.0% (0.01 < CosΦ < 0.1)

4. Insulation Strength

1) Insulation resistance between voltage/current input terminals and chassis ≥ 100MΩ.

2) Withstands 2kV (rms) power frequency voltage between power input terminals and chassis for 1 minute.

 

Product feature and application

 

1. It can measure no-load current, no-load loss, short-circuit voltage and load loss of transformers, covering core electrical indicators.

2. Harmonic detection capability covers 1~31st order, meeting the demand for high-precision harmonic analysis.

3. Built-in automatic range switching, wide-range measurement combined with extremely simple wiring, reducing operation difficulty.

4. Automatically verifies wiring during three-phase transformer tests, and synchronously displays three-phase voltage and current phasor diagrams to avoid wiring errors.

5. Supports single-watt and three-watt impedance testing, and can measure basic parameters such as three-phase AC/DC voltage, current, active/reactive power, and frequency.

6. Equipped with automatic correction of waveform, temperature, non-rated voltage/current, improving the accuracy of detection results.

7. 320×240 high-brightness LCD screen, full Chinese menu and touch buttons, wide temperature adaptation for four-season use.

8. Can preset 40 sets of sample parameters, support addition, deletion and modification, adapting to batch detection scenarios.

9. Equipped with USB interface, which can connect external U disk to export data and upgrade firmware.

10. Built-in real-time clock, automatically records test time, stores 500 sets of test data when power is off, and supports online transmission.

11. Panel-mounted thermal printer, which can quickly print test reports on-site.

12. Can connect external voltage and current transformers to expand the range, meeting the detection needs of large-scale equipment.

 

Prodection details

 

   Suitable for power generation enterprises, industrial and mining enterprises, scientific research institutes and other institutions. It can carry out no-load, load and harmonic tests on single-phase/three-phase transformers, complete parameter calibration, data storage and analysis, and meet the needs of transformer factory testing, on-site operation and maintenance, and laboratory research.

 

Company Qualifications

 

 

FAQ

1)How does the MOEORW-W4300 Transformer Parameter Tester determine correct wiring during three-phase transformer no-load testing?

Answer: During three-phase transformer no-load testing, the upper left corner of the test data page displays a phasor diagram of the test voltage and current. If wiring is correct, the phasor diagram displays normally. If wiring is incorrect, the page will directly prompt "Wiring error, please power off and check," helping users quickly troubleshoot wiring issues.

2)What data export and storage-related functions does the MOEORW-W4300 Transformer Parameter Tester support?

Answer: The instrument's data-related functions include: 1. USB interface for connecting USB drives to export data and upgrade software; 2. Built-in real-time clock automatically records test date and time for convenient result management; 3. Power-off storage and browsing capability, storing up to 500 test result sets; 4. Supports data transfer via computer connection; 5. Equipped with a panel-mounted thermal printer for rapid on-site printing of test results.

3)How should the MOEORW-W4300 Transformer Parameter Tester be handled if the screen suddenly goes black during operation?

Answer: If the screen suddenly goes black during use, press the instrument's reset button directly and restart the measurement. This troubleshooting method is sourced from the product manual's common troubleshooting section and can quickly resolve screen blackout issues not caused by hardware damage.

 

Hot Tags: transformer parameter tester, China transformer parameter tester manufacturers, factory, Transformer Parameter Tester, Transformer Core No Load Test Device, Transformer No Load Loss Tester, Transformer Loss Parameter Comprehensive Tester, Intelligent Transformer Loss Parameter Tester, transformer load and no load loss tester