Product Introduction
MOEORW-WGS05 three-phase frequency tripling power generator is specially designed for induced withstand voltage test of transformers, mutual inductors, generators and motors. It adopts three single-phase transformers with star-connected primary windings and open delta-connected secondary windings, which can output stable 150Hz three-fold frequency voltage to meet the vertical insulation test requirements of winding inter-turn, inter-layer, inter-section and inter-phase insulation. It features simple operation, reliable performance and good adaptability to various test loads, and is an ideal equipment for electrical equipment insulation withstand voltage test.
Product Parameter (specification)
| Input Voltage | 220V/380V,50Hz |
| Output Voltage | 50-500V (max 750V), 100-1000V (max 1500V), 150Hz |
| Waveform | Sine wave,Distortion rate<1% |
| Capacity | 1-1000KVA |
| Load Type | Resistive, inductive, capacitive |
| 5KVA Model | Input 220V,Output 400V/20A,450×250×320mm,40kg |
| 12KVA Model | Input 380V,Output 560V/25A,490×260×335mm,78kg |
Product Feature
- Adopt three single-phase transformer combination structure, stable three-fold frequency output
- Open delta connection eliminates fundamental frequency component, pure 150Hz frequency output
- Equipped with special control device, with voltage regulation, current and voltage monitoring function
- Built-in over-current relay protection, automatic power off when breakdown occurs
- Suitable for resistive, inductive and capacitive loads, with external compensation interface
- Split structure, easy for on-site wiring and test operation
Product Application
- Induced withstand voltage test of power transformer winding insulation
- Inter-turn and inter-layer insulation test of voltage/current transformer
- Induced insulation test of generator and motor stator windings
- Factory inspection and preventive test of electrical equipment insulation performance
- Power construction, electrical maintenance and quality inspection department test use
Company Qualifications
FAQ
Q: What kind of load does this model apply to?
A: It is suitable for resistive, inductive and capacitive loads. Capacitive loads can be used without external compensation or with inductive compensation; inductive loads need capacitive compensation (about 50% of load capacity).
Q: What is the operation process?
A: Connect power and ground → return voltage regulator to zero → start operation → boost to test voltage → monitor data → test completion → return voltage regulator to zero and shut down.
Hot Tags: gs05 150hz three-frequency power generator, China gs05 150hz three-frequency power generator manufacturers, factory, SF6 Leakage Detection Device