Integrated Overvoltage Protector Tester

Send Inquiry
Integrated Overvoltage Protector Tester
Details
MOEORW-W2100MX is specially designed for gap-type zinc oxide overvoltage protectors, accurately measuring power frequency discharge voltage.
It automatically detects discharge, cuts off high voltage quickly, and provides full safety protection with simple operation.
With a built-in high-voltage power supply, it is portable and durable, suitable for on-site rapid testing and acceptance tests.
Category
High Voltage Test System
Share to
Description

Product Introduction

 

Overvoltage protector testers are widely used for testing the power frequency discharge voltage of various electrical equipment, and are especially effective for testing the power frequency discharge voltage of zinc oxide overvoltage protectors with gaps (also known as surge arresters or TBPs).

 

This tester uses a new type of special circuit to monitor the test voltage waveform and simultaneously acquire the discharge pulse signal of the current loop. It automatically determines the gap discharge, locks the effective voltage value at the moment of discharge, and quickly cuts off the test power supply to protect the test sample and test equipment from overcurrent damage.

 

This testing instrument is small in size, lightweight, shockproof and drop-resistant, easy to operate, and portable.

 

Product Parameter (specification)

 

Output Voltage 0-30kV RMS
Output Current 0-25mA RMS
Discharge Detection Method Waveform detection, Fourier transform
Voltage Accuracy ±(reading×1%+0.1kV)
High Voltage Cut-off Time <0.2s
Resolution 0.01kV
Input Power AC220V±10%,50Hz±1%,mains/generator power
Ambient Temperature -10℃~70℃
Relative Humidity <90%
External Dimension 390×320×350mm
Weight 21kg

 

Product Feature

 

  • The instrument monitors the discharge current in real time using waveform and current detection methods. When a discharge current is detected, it is recorded immediately . At this moment, high voltage is applied, and the high-voltage power supply is cut off within 0.2 seconds . The instrument provides high accuracy and stable test results.
  • The instrument features a large LCD screen and is easy to operate. The testing process is guided by English menu prompts , requiring no additional professional training for operators.
  • This all-in-one model features a built-in high-voltage power supply, facilitating on-site testing and reducing the need for on-site wiring.
  • High voltage protection: If the test sample is short-circuited, broken down, or experiences high voltage current fluctuations, the output can be cut off at high speed via a short circuit.
  • High-voltage cables are high-voltage resistant insulated conductors. To ensure data accuracy, please conduct the suspension test .
  • Preventing misoperation: Real-time monitoring of voltage and current ; clear distinction between high and low voltage at the terminals ; slow voltage increase and rapid voltage decrease with audible alarm.
  • Grounding protection: The instrument cannot work properly if it is poorly grounded or not grounded.

 

Product Application

 

  • Power field **Zinc oxide surge arrester with gap (TBP)** power frequency discharge voltage test
  • Power frequency discharge voltage testing and acceptance tests for various electrical equipment
  • Portable on-site testing for power operation, maintenance, and testing units

 

Company Qualifications

 

 

FAQ

 

Q: What happens if the overvoltage protector tester has a poor grounding?

A: The instrument will indicate a grounding abnormality and will be unable to start the test. It must be reliably grounded before it can be restarted to work normally.

Q: Why is there a 15-second interval between tests using a zinc oxide overvoltage protector detector?

A: This ensures the sample is fully deionized and residual charge is eliminated, guaranteeing stable and accurate test data for each test.

Q: How do I export test results from an overvoltage protector tester to a USB flash drive?

A: Insert the USB flash drive; the instrument will automatically recognize it. Go to Data Management, select "Export Data to USB Flash Drive," and wait for the export success message.

Q: How do I set the protection voltage and protection current on a surge arrester discharge tester?

A: Enter the test interface, select the parameter using the function mouse and click, rotate to adjust the value, and click confirm again; the recommended protection current setting is 2mA.

Q: Will the overvoltage tester automatically cut off power after the sample breaks down?

A: Yes. Upon detecting a discharge, the instrument will automatically cut off the high voltage within 0.2 seconds to protect the sample and equipment.

 

Hot Tags: integrated overvoltage protector tester, China integrated overvoltage protector tester manufacturers, factory, SF6 Leakage Detection Device

Send Inquiry