High-Precision Portable Power Quality Analyzer

Send Inquiry
High-Precision Portable Power Quality Analyzer
Details
MOEORW-WNQ66 Class A power quality analyzer enables full-spectrum grid disturbance testing for field audits. Multi-channel recording and remote data access simplify long-term monitoring and fault tracing. Built-in rechargeable battery delivers reliable, PC-free measurements across industrial and renewable sites.
Category
Electric Energy Test Equipment
Share to
Description

Product Overview

 

The MOEORW-WNQ66 power quality analyzer is a portable industrial measuring terminal independently developed with PICOLINUX embedded system, designed for comprehensive grid power quality monitoring, recording, transient waveform capture and data analysis. The device is equipped with 4 voltage and 4 current independent sampling channels, supporting multi-system wiring modes for single-phase, two-phase and three-phase power grids. It integrates real-time data display, steady-state event recording, transient wave recording, multi-network communication and local data storage functions, fully meeting field inspection, grid acceptance, equipment failure diagnosis and long-term unattended monitoring demands of power distribution, industrial manufacturing and new energy stations.


The unit adopts an 8-inch industrial touch display with built-in 8000mAh rechargeable lithium battery, supporting up to 6 hours of continuous offline operation. Multiple communication interfaces including Ethernet, Wi-Fi, 4G, RS232 and USB OTG are reserved for remote data transmission and device interconnection. All measurement performance meets Class A harmonic testing standards, with complete EMC anti-interference compliance for harsh on-site electromagnetic environments.

 

Technical Specifications

 

General Mechanical & Display Parameters

Item

Technical Index

Overall Dimension

246×205×73 mm

Net Weight

2.2 kg

Display Screen

8-inch TFT touch screen

Screen Resolution

800 × 600

Typical Max Brightness

350 cd/m², adjustable

Contrast Ratio (Typ.)

500:1

Viewing Angle (L/R/U/D, CR≥10)

70°/70°/50°/70°

 

Power Supply Parameters

Item

Technical Index

Mains Input

AC 220V

Adapter Output

DC 12V / 3A

Built-in Battery

8000mAh rechargeable lithium battery

Continuous Battery Runtime

6 hours

Full Charging Time

2.5 hours

Power-saving Function

Adjustable LCD backlight brightness & standby timeout

 

Storage & Communication Interfaces

Item

Technical Index

Storage Medium

SD card, standard 32GB, expandable to max 64GB

Wired Ethernet

1-port 10/100 Mbps adaptive

Wireless Communication

Wi-Fi + built-in 4G module

External Interface

USB OTG, 1-channel RS232 serial port

 

Environmental & EMC Performance

Item

Technical Index

Operating Temperature

0℃ ~ +45℃, relative humidity ≤90% non-condensing

Storage Temperature

-20℃ ~ +50℃, relative humidity ≤95% non-condensing

Common Mode Rejection Ratio

CMRR > 60 dB

Voltage Channel Crosstalk

-60 dB at nominal frequency

Storage Circuit Crosstalk

-95 dB at nominal frequency

EMC Compliance Standards

GB/T 17626 series electrostatic discharge, RF radiation, EFT, surge, magnetic field immunity tests

Environmental Reliability Standards

GB/T 2423 series low/high temperature, alternating damp heat, shock, vibration & temperature cycling tests

 

Input Channel & Measurement Basic Parameters

Item

Technical Index

Sampling Channels

4 voltage channels, 4 current channels

Voltage Channel Nominal Ranges

120V / 230V / 400V / 1000V

Current Channel Access Condition

Compatible with current clamps outputting voltage signal, peak output voltage ≤10V

Fundamental Grid Frequency

50 Hz

Supported Wiring Topologies

1P2W (with/without neutral), 2P3W, 3P3W (IT/Delta/Element), 3P4W Wye

 

Measurement Range & Accuracy

Measured Parameter

Range & Precision Index

Grid Frequency

45 ~ 65 Hz, accuracy ±0.01 Hz

Voltage RMS

Range:120/230/400/1000V, resolution 0.01V, accuracy ±0.1% of nominal voltage

Current RMS

Accuracy ±0.2%; range depends on matched current clamp (5A/50A/100A/500A clamp, 1200A/3000A/6000A current loop; standard 5A clamp supplied)

Harmonic Measurement

0~63 orders, complies with Class A standard, 10-cycle sampling window

Active/Reactive/Apparent Power

Accuracy ±0.5% reading

Power Factor

-1.000 ~ 1.000, resolution 0.001, accuracy ±0.5%

Voltage Unbalance Degree

±0.2%

Current Unbalance Degree

±0.5%

Short-term Flicker Pst

Range 0~20, accuracy ±5%

Fundamental Phase Angle

0° ~ 360°, accuracy ±1°

Transient Amplitude

Accuracy ±0.5%

Transient Time Stamp

Accuracy ±1 ms

 

Core Functions & Features

 

Hardware Design & Hardware Configuration
1.Multi-channel synchronous sampling architecture with 4 voltage and 4 current independent input channels, compatible with full range of external current clamps with voltage output signals.
2.8-inch high-brightness industrial touch screen with adjustable backlight, supporting screenshot, one-click screen lock and brightness cycle adjustment via physical shortcut keys.
3.Multi-mode power supply solution combining external 12V adapter and built-in large-capacity lithium battery, supporting long-duration field measurement without mains power access.
4.Rich multi-type communication interfaces including Ethernet, Wi-Fi, 4G, RS232 and USB OTG, realizing wired/wireless remote data transmission and host computer linkage.
5.Standard SD card mass storage design, supporting up to 64GB expandable storage for long-term data logging, waveform recording and screenshot file storage.
6.Dual status indicator lamps (power & recording) to intuitively display battery charging state and SD card data read-write activity.
 

Measurement Performance Advantages
1.Full Class A harmonic measurement performance, supporting DC component and 1~63 order harmonic voltage, current and harmonic power analysis.
2.High-precision flicker measurement module, simultaneously calculating short-term flicker Pst (10min) and long-term flicker Plt (2h) to meet grid fluctuation assessment requirements.
3.Complete three-phase unbalance analysis function, calculating positive/negative/zero sequence voltage & current components and corresponding unbalance degrees.
4.Built-in transient event capture algorithm, automatically recording voltage swell, voltage dip, short interruption and impulse current events with front/rear waveform cycles configurable.
5.High-precision power and energy statistics, separately calculating phase & total active/reactive/apparent energy and four-quadrant reactive energy accumulation.
6.Ultra-wide frequency measurement range covering 45–65Hz, applicable to conventional power grids and variable frequency power supply systems.
 

Practical On-site Application Value
1.Multi-type data visualization display including data tables, real-time trend curves, harmonic bar charts, oscilloscope waveforms and phasor vector diagrams for intuitive fault judgment.
2.Two independent recording modules: Recorder for steady-state parameter timing logging, Wave Recorder for raw voltage/current waveform continuous capture up to 10 minutes, both supporting unattended scheduled recording tasks (max 6 scheduled tasks).
3.Customizable steady-state and transient alarm thresholds complying with GB/T 14549, GB/T 12325 national standards, automatic snapshot storage of abnormal event data for post-fault tracing.
4.Independent parameter configuration module, supporting PT/CT ratio setting, wiring topology switching, current clamp model matching and measurement point information recording; config files can be imported/exported for rapid scene switching.
5.System self-management functions including network configuration, SD card file management, system time synchronization (manual/NTP/GPS), multi-language switching, screen lock password setting and system upgrade.
6.Offline operation capability without PC connection; all measurement data stored locally on SD card, files can be exported via USB or remotely transmitted via network to Picoviewer host software for secondary analysis.

 

Application Scope

 

1.Power Grid Operation & Maintenance: Distribution station power quality inspection, grid voltage fluctuation, harmonic and three-phase unbalance monitoring.
2.Industrial Manufacturing Plant: Non-linear load (frequency converter, welding equipment, switching power supply) power pollution testing, transformer overheating risk assessment.
3.New Energy Power Station: Photovoltaic, wind power grid-connection power quality acceptance, transient voltage disturbance monitoring during grid-connected switching.
4.Commercial Complex & Data Center: Power supply stability testing, flicker and power factor optimization inspection.
5.Electrical Equipment Factory: Generator, transformer, high/low voltage switchgear factory power quality type test.
6.Construction & Transportation: Subway, port, large construction site temporary power supply real-time monitoring and long-term data recording.

 

Applicable Standards & Compliance

 

Power Quality Measurement Standards
1.GB/T 14549-1993: Quality of Electric Energy Supply – Harmonics in Public Supply Network
2.GB/T 12325: Power Quality – Deviation of Supply Voltage
 

EMC Immunity Standards (GB/T 17626 Series)
1.GB/T 17626.2 Electrostatic Discharge Immunity Test (Level 4)
2.GB/T 17626.3 Radiated Radio Frequency Electromagnetic Field Immunity Test (Level 3)
3.GB/T 17626.4 Electrical Fast Transient Burst Immunity Test (Level 4)
4.GB/T 17626.5 Surge Immunity Test (Level 4)
5.GB/T 17626.8 Power Frequency Magnetic Field Immunity Test (Level 4)
6.GB/T 17626.9 Pulsed Magnetic Field Immunity Test (Level 5)
7.GB/T 17626.12 Oscillatory Wave Immunity Test (Level 3)
 

Environmental Reliability Test Standards (GB/T 2423 Series)
Low temperature, high temperature, alternating damp heat, shock, vibration, temperature change test standards

 

Product Structure & Standard Accessories

 

Host Terminal Interface Layout
1.Top side: 4 current measurement channels
2.Side panel: 4 voltage measurement channels, ground terminal, RS232, Ethernet, power input, USB OTG, SD card slot, SIM card slot, indicator lamps
3.Front panel: 8-inch touch screen, physical shortcut keys (power, screenshot, screen lock, brightness adjustment)

 

Standard Accessories (Not Listed in Manual, Omitted)
No official standard accessory list provided in the operation manual; matching current clamps, test leads and power adapter shall be selected according to on-site measurement requirements.

 

Operation, Storage & Daily Maintenance

 

Daily Operation Safety Rules
1.Read the full operation manual before deployment; avoid operation alone in live measurement environments.
2.Prohibit use near flammable and explosive gas mixtures.
3.Inspect insulation integrity of host, test leads and current clamps before each measurement; replace damaged accessories immediately.
4.Do not input voltage/current signals exceeding the rated range of the analyzer, probes or current clamps.
5.Disconnect power of the tested equipment or wear protective clothing during installation and removal of test clamps.
6.Ground terminal is only used for equipment grounding; no external voltage shall be applied to the ground port.
7.Avoid inserting metal foreign objects into BNC or banana plug ports.

 

Storage Maintenance Requirements
1.Clean the equipment surface with dry soft cloth only; corrosive solvents, alcohol and cleaning agents are forbidden to prevent surface text and coating damage.
2.For long-term storage, fully charge the built-in lithium battery before storage; supplementary charging at least once every 12 months to maintain battery performance.
3.Stop measurement and charge immediately when low battery warning pops up; frequent shallow charging shall be avoided, charge only when low power reminder is triggered.
4.Store within specified temperature and humidity range, avoid direct sunlight and heavy damp environment.

 

Data Storage Maintenance
1.Do not extract SD card during recorder or wave recorder operation to prevent data loss and abnormal system operation.
2.SD card formatting must be completed via the built-in formatting function of the analyzer; PC formatting is prohibited.
3.When SD card remaining capacity ≤1.6GB, the system will display low storage reminder; new recording/wave recording tasks cannot be created when remaining capacity <640MB, and running tasks will be forced to terminate automatically at 640MB residual space.
4.All recorded data, screenshots and configuration files are stored on SD card; the manufacturer takes no responsibility for data loss caused by SD card damage.

 

FAQ

 

Q1: The recorder stops recording automatically midway, what are the possible causes?

A: 1. SD card remaining capacity drops below 640MB, system forced termination;

2. Low battery power triggers automatic shutdown;

3. SD card loose or damaged;

4. System time or parameter modified during recording.

Q2: Transient events cannot be captured during field measurement, how to troubleshoot?

A: 1. Verify transient threshold parameters (voltage swell/dip/interruption, impulse current ratio) are set according to actual working conditions;

2. Check front/rear waveform cycle configuration in transient parameter menu;

3. Confirm wiring of voltage and current channels is correct without loose clamps.

Q3: The device cannot connect to 4G network after inserting SIM card?

A: 1. Restart the terminal after SIM card insertion;

2. Check SIM card balance and signal coverage at measurement site;

3. Confirm mobile network switch is enabled in Connection Management page.

Q4: Screen display is dim and cannot adjust brightness?

A: Press the dedicated brightness shortcut key to cycle brightness levels; if ineffective, check battery power, low battery will limit maximum screen brightness.

Q5: Cannot import/export parameter configuration files?

A: Confirm SD card is inserted normally with sufficient storage space; enter File Management page to check .conf configuration file integrity, avoid modifying files via external PC.

Q6: Harmonic measurement data appears abnormal distortion?

A: 1. Check current clamp model selection matches the actual clamp used;

2. Recheck PT/CT ratio setting in main parameter page;

3. Reinstall test clamps to eliminate poor contact interference.

Q7: System time synchronization fails when using NTP automatic calibration?

A: 1. Verify Ethernet/Wi-Fi/4G network connection is normal;

2. Switch alternative NTP time server address in Time Management page;

3. Check on-site network firewall blocking time synchronization port.

Q8: Can recording and wave recording tasks run in the background while exiting the application page?

A: Yes, both modules support background operation; do not remove SD card or modify system parameters during background recording.

 

Hot Tags: high-precision portable power quality analyzer, China high-precision portable power quality analyzer manufacturers, factory, Energy Meter Field Calibrator, Meter Calibration Test Bench, Multifunction Calibrators, Three Phase Energy Meter Test Bench, Three Phase Power Analyzer, Three Phase Source