Three-Phase Multifunctional Electrical Tester
Product Introduction
Model MOEORW‑WND35 acts as high‑precision portable AC power testing hardware built for field‑side metering validation and comprehensive AC parameter acquisition. Two accuracy grades are available: Class 0.2 serves as on‑site calibrator for three‑phase energy meters, whereas Class 0.5 works as integrated inspection unit for three‑phase power consumption auditing.
Powered by combined 32‑bit ARM & DSP processing chips plus multi‑channel 16‑bit high‑resolution A/D sampling modules, this tester integrates internal wide‑range high‑accuracy current transformers. Users may attach external current clamps to broaden measuring coverage, securing reliable precision across diverse field conditions. It suits on‑site meter validation, power grid inspection, power quality diagnostics and hands‑on skill training for utility maintenance crews.
Key practical highlights include multi‑variable synchronous acquisition, smart wiring diagnosis & error compensation, onboard data logging & outbound transmission, dual‑source power architecture for prolonged runtime, alongside hybrid touch‑screen plus physical‑button human‑machine interaction.
Product Parameter (specification)
| Item | Parameters | Item | Parameters |
|---|---|---|---|
| Voltage measuring range | 5V~500V | 5A‑rated Clamp Current Range | 5mA‑10A |
| Voltage resolution | 0.001V | Current resolution(5A clamp) | 0.0001A |
| Voltage allowable error | ±0.5 % ±0.2% | Current error(5A clamp) | ±0.5% |
| Frequency coverage | 45‑65Hz | Active energy & power(5A clamp) | ±0.5 % |
| Frequency readout resolution | 0.01 Hz | Reactive energy & power(5A clamp) | ±0.5 % |
| Frequency deviation limit | ±0.03 Hz | Optional heavy‑current clamps | 100A / 500A /1000A |
| Phase‑angle test scope | 0°‑360° | Current error (large‑current clamp) | ±0.5% |
| Phase resolution | 0.01° | Active energy & power(large‑current clamp) | ±0.5% |
| Phase measuring error | ±1.0° | Reactive energy & power(large‑current clamp) | ±1.0% |
| Harmonic acquisition | 2nd ~31st order | CT ratio measurement tolerance | ±0.5 % |
| Pulse constant‑5A | 1.8×10⁷ P/kWh | Voltage influence deviation | ± 0.05 % |
| Pulse constant‑100A | 1.8×10⁶ P/kWh | Frequency‑caused deviation | ± 0.01 % |
| Pulse constant‑500A | 3.6×10⁵ P/kWh | Temperature drift coefficient | <5ppm/ ℃ |
| Pulse constant‑1000A | 1.8×10⁵ P/kWh | 24‑hour long‑term drift | ± 0.05 % |
Safety Ratings
Dielectric withstand: Voltage input ports, AC charging socket against chassis shell, as well as current‑clamp cores, connecting leads and handles sustain 1kV /50Hz sinusoidal AC for 60 seconds. Insulation resistance: Above 100MΩ under 1kV test voltage among above‑mentioned test interfaces.
Mechanical Dimensions & Weight
Main instrument unit: 275×200×72 mm, net weight:1.5 kg
Single clamp‑on current transformer:140×40×19 mm, 0.160 kg per piece
Full set (with accessories):423 × 336 × 126 mm, total weight:6.5 kg /set
Accessory storage case:280 × 235 × 130 mm, weight:1.5 kg /set
Environmental Operating Conditions
Working ambient:‑15℃ ~ +45℃; relative humidity ≤90%RH
Storage condition:‑30℃ ~ +60℃; storage humidity ≤95%RH
Applicable altitude: below 1500 meters
Power Supply Options
AC PT measurement‑loop power feed: AC80V‑480V, power draw 7.5VA
External mains inlet socket: AC220V 50Hz
Rechargeable lithium‑ion pack: 2.2Ah /7.4V×2; charging duration ≥8 hours; cycle lifespan ≥500 times
Product features and applications
7‑inch TFT true‑color LCD panel (800*480 dots). Graphical UI supports touch operation together with hardware push‑buttons for intuitive readout.
Auto‑ranging measurement eliminates manual range shifting.
Dual‑channel pulse input supports simultaneous reference‑meter & test‑meter comparison for active/reactive energy meter verification.
Error trend trace function outputs visualized error curve diagrams and real‑time monitoring datasets.
Compatible calibration targets: single‑phase / three‑phase active & reactive electronic watt‑hour meters, standard reference meters, induction mechanical meters, electro‑mechanical combined units, prepaid meters and multi‑function smart meters.
Supports multiple wiring topologies including single‑phase, three‑phase Y‑connection and delta‑connection for AC voltage, current, active/reactive/apparent power acquisition.
Rich parameter collection: AC voltage, current, multi‑type power values, energy reading, frequency, phase angle, power factor, waveform distortion rate, pulse constant for DUT, low‑voltage CT transformation ratio and angular difference.
Capture 2‑31st harmonic magnitude & content for voltage/current, render harmonic histogram visualization.
Auto fault‑detection for P3/P4 three‑phase meter wiring mistakes; pinpoints faulty segments, renders secondary wiring sketch plus power calculation formula and computes correction coefficient automatically.
Wiring simulation module: generate virtual wiring outcomes derived from field‑collected data without actual voltage/current feeding; works as practical training tool to boost technicians' wiring‑check proficiency.
Three alternative power‑stabilizing computation algorithms for noisy field environments.
Load trend logging: users may select four metrics out of voltage, current, frequency, power and power factor for continuous trend recording.
Cumulative energy counting and runtime timing function embedded; voltage unbalance factor computation available.
Built‑in vector arithmetic tool assists on‑site vector summation calculation for voltage‑current groups.
Fit optional 500A+ current clamps to complete real‑load comprehensive error assessment for low‑voltage metering assemblies.
Dual‑power mode: draw operating power directly from 80‑450V AC measuring terminals or run off internal 7600 mAh high‑capacity lithium‑battery pack.
Internal memory stores maximum 4000 groups of test logs; historical datasets and vector graphs can be reviewed locally.
Pre‑installed standard English font library; smart input engine supports entry of Chinese characters, alphabets and numeric labels for saved records.
USB port enables dataset export to PC via flash‑disk. Host‑side software allows browsing, modification, A4‑format standardized test‑report printing and instrument‑data backup.
RS‑485 communication port reads energy‑register data from multi‑function meters following national GB/T 645 protocol.
Optional Bluetooth wireless connectivity: pair with dedicated Android APP for remote data acquisition, real‑time observation, storage and analytics via handheld terminals. Mobile terminals support on‑site evidence capture including photographing and GPS geotagging.
Prodection details
On-site calibration of various single-phase and three-phase energy meters, including dual-channel pulse calibration of main and auxiliary meters, and detection of reading/energy error.
Measurement of electrical parameters such as voltage, current, and power, and detection of unbalance and stability under single-phase/three-phase multi-connection configurations.
Identifying wiring errors in electricity meters, measuring low-voltage CT ratio/angle difference, and troubleshooting overall errors in metering devices.
Voltage/current 2nd to 31st harmonic measurement, waveform distortion detection, power quality analysis
On-site data acquisition, storage, and export; supporting software for generating test reports; and 645 protocol for reading meter data.
Wiring simulation is used for training electrical workers in wiring inspection skills.
Q: Are you a factory or a trading company?
We are a professional manufacturer of testing equipment.
Q: How is the after-sales service?
A: The warranty period is 12 months. After the warranty period, we also provide lifetime service paidrepair or service.
Q: How is the after-sales service?
A: The warranty period is 12 months. After the warranty period, we also provide lifetime service paidrepair or service.
Q: What about transportation?
A: It depends on your requirements. We can ship to your airport by air, to your seaport by sea, or to your office by courier.
We also accept cooperation with your shipping agent.
Q: Are your keyboard, interface, software, and manuals in English?
A: Yes, if you are using the English version of the keyboard, interface, software, and manual and require other languages, please contact us for confirmation.
Hot Tags: three-phase multifunctional electrical tester, China three-phase multifunctional electrical tester manufacturers, factory, Double Clamps Digital Phase Meter, Three phase clamp on phase voltmeter, Power Quality Analyzer, Meter Calibration Test Bench, Energy Meter Field Calibrator, Three Phase Energy Meter Test Bench