Transformer Field Calibration Device
Product Introduction
MOEORW-W8050/35 Portable Instrument Transformer Calibration Unit is a new-generation portable instrument transformer testing device developed by our company. It serves as an ideal testing equipment for power measurement in sectors such as power systems, metallurgy, railways, and chemical industries. This unit is easy to carry and features simple wiring, enhancing testing efficiency during indoor and outdoor experimental operations.
Product Parameter (specification)
|
1. Environmental Conditions for Device Operation |
|
|
Temperature |
5°C to 40°C Relative Humidity;<80% (at 25°C) Altitude;<2500m |
|
Power Frequency |
50Hz ± 0.5Hz Power Voltage;220V ± 5V |
|
2. Portable Transformer Calibration Device Parameters |
|
|
2.1 Measurement Range |
|
|
In-phase Component (%) |
0.0001 to 199.9 Resolution;0.0001 |
|
Quadrature Component (minutes) |
0.001 to 599.9 Resolution;0.001 |
|
Impedance () |
0.0001~60.0 Resolution;0.0001 |
|
Admittance (ms) |
0.0001~60.0 Resolution;0.0001 |
|
2.2 Basic Error |
|
|
In-phase Component |
X = (X × 2% + Y × 2% 2 digits) |
|
Quadrature Component |
Y = (X × 2% + Y × 2% 5 digits) "X", "Y" - Instrument display values "5 digits" - Instrument quantization error |
|
Percentage Meter |
Class 1 |
|
2.3 Operating Range |
|
|
Current |
(1%–149%) In (In=5A);(5%-149%)In (In=1A) |
|
Voltage |
(5%-149%)Un (Un=100V, 150V, 100V/);(5%-199%)Un (Un=100V/3) |
|
2.4 Operating Load |
|
|
Current |
To for Tx < 0.12 cos = 1 |
|
Voltage |
a for x < 0.25VA (100V) |
|
2.5 Polarity Error Indication |
|
|
When the error exceeds 180% at 5% or more of the rated operating current (voltage), a polarity indication should occur. |
|
|
Note;If the error exceeds 10% of the rated operating current (voltage) and the required polarity indication still does not appear, this indicates a software fault. Do not increase the current (voltage) further to avoid damaging the instrument. |
|
|
2.6 Turns Ratio Error Indication |
|
|
When the error exceeds 30% but is less than 180% of the rated operating current (voltage) at 5% or above, a turns ratio error indication should be provided. |
|
Product feature and application
1) Advanced hardware architecture. Utilizes high-performance 32-bit floating-point DSP and high-performance A/D chips to achieve precise signal computation.
01
2) Comprehensive and practical test function modules meet diverse user testing requirements. Can be used independently or integrated with our latest high-speed instrument transformer calibration bench.
02
3) Features a high-resolution large-screen LCD display with an English menu interface that is more user-friendly and aesthetically pleasing. The humanized interface design enables more convenient and efficient operation.
03
4) The entire instrument features a plastic profile chassis, offering compact internal dimensions, lightweight construction, and easy portability.
04
5) Dual hardware/software
05
Prodection details
Suitable for power measurement scenarios in industries such as power generation, metallurgy, railways, and chemical engineering, it meets the requirements for both on-site testing indoors and outdoors as well as laboratory calibration. It is used for verifying the characteristic parameters of current transformers (CTs) and voltage transformers (PTs).