Transformer Field Calibration Device

Send Inquiry
Transformer Field Calibration Device
Details
The Next Generation of Intelligent Calibration Tools! The MOEORW-W8050/35 Portable Transformer Calibration Device features advanced digital filtering and Fourier algorithms, paired with a high-definition LCD interface. It delivers precise measurements and rapid response times, capable of standalone or networked operation. This device provides an efficient, intelligent solution for power metering.
Category
CT PT Analyzer
Share to
Description

Transformer Field Calibration Device

 

Product Introduction

 

MOEORW-W8050/35 Portable Instrument Transformer Calibration Unit is a new-generation portable instrument transformer testing device developed by our company. It serves as an ideal testing equipment for power measurement in sectors such as power systems, metallurgy, railways, and chemical industries. This unit is easy to carry and features simple wiring, enhancing testing efficiency during indoor and outdoor experimental operations.

 

Product Parameter (specification)

 

1. Environmental Conditions for Device Operation

Temperature

5°C to 40°C Relative Humidity;<80% (at 25°C) Altitude;<2500m

Power Frequency

50Hz ± 0.5Hz Power Voltage;220V ± 5V

2. Portable Transformer Calibration Device Parameters

2.1 Measurement Range

In-phase Component (%)

0.0001 to 199.9 Resolution;0.0001

Quadrature Component (minutes)

0.001 to 599.9 Resolution;0.001

Impedance ()

0.0001~60.0 Resolution;0.0001

Admittance (ms)

0.0001~60.0 Resolution;0.0001

2.2 Basic Error

In-phase Component

X = (X × 2% + Y × 2% 2 digits)

Quadrature Component

Y = (X × 2% + Y × 2% 5 digits)

"X", "Y" - Instrument display values

"5 digits" - Instrument quantization error

Percentage Meter

Class 1

2.3 Operating Range

Current

(1%–149%) In (In=5A);(5%-149%)In (In=1A)

Voltage

(5%-149%)Un (Un=100V, 150V, 100V/);(5%-199%)Un (Un=100V/3)

2.4 Operating Load

Current

To for Tx < 0.12 cos = 1

Voltage

a for x < 0.25VA (100V)

2.5 Polarity Error Indication

When the error exceeds 180% at 5% or more of the rated operating current (voltage), a polarity indication should occur.

Note;If the error exceeds 10% of the rated operating current (voltage) and the required polarity indication still does not appear, this indicates a software fault. Do not increase the current (voltage) further to avoid damaging the instrument.

2.6 Turns Ratio Error Indication

When the error exceeds 30% but is less than 180% of the rated operating current (voltage) at 5% or above, a turns ratio error indication should be provided.

 

Product feature and application

 

1) Advanced hardware architecture. Utilizes high-performance 32-bit floating-point DSP and high-performance A/D chips to achieve precise signal computation.

01

2) Comprehensive and practical test function modules meet diverse user testing requirements. Can be used independently or integrated with our latest high-speed instrument transformer calibration bench.

02

3) Features a high-resolution large-screen LCD display with an English menu interface that is more user-friendly and aesthetically pleasing. The humanized interface design enables more convenient and efficient operation.

03

4) The entire instrument features a plastic profile chassis, offering compact internal dimensions, lightweight construction, and easy portability.

04

5) Dual hardware/software

05

 

Prodection details

 

Suitable for power measurement scenarios in industries such as power generation, metallurgy, railways, and chemical engineering, it meets the requirements for both on-site testing indoors and outdoors as well as laboratory calibration. It is used for verifying the characteristic parameters of current transformers (CTs) and voltage transformers (PTs).

 

Company Qualifications

 

 

FAQ

1)What are the features of the operating interface for the MOEORW-W8050/35 portable instrument transformer calibrator?

Answer: This device features a high-resolution large-screen LCD display (resolution 320×240 dots) with a Chinese menu interface. Its design is user-friendly, aesthetically pleasing, and easy to operate. The main interface clearly displays key parameters such as the measurement object, secondary current/voltage, and accuracy class. Parameters can be modified via buttons or a computer. Measurement modes (standalone/networked, manual/automatic) can be switched according to requirements. All operations feature on-screen prompts, ensuring low learning difficulty.

2)What safety requirements must be met when using the MOEORW-W8050/35 portable transformer tester?

Answer: Core safety requirements include:
- Use only dedicated, specification-compliant power cords;
- Do not arbitrarily plug or unplug test leads connected to live terminals;
- Prohibit operation without the instrument cover, in damp environments, or in explosive atmospheres; Use fuses of the specified type and rating; avoid touching exposed circuits or live metal parts when the device is energized; cease operation and contact the manufacturer for repair if device damage is suspected; ensure all relevant terminals are reliably grounded and use a three-pin single-phase power plug to minimize interference.

3)Can the MOEORW-W8050/35 Portable Transformer Calibrator be used independently or does it require other equipment? What measurement objects does it support?

Answer: This device can be used independently or in conjunction with the manufacturer's high-speed transformer calibration bench. Measurement objects include current transformers, voltage transformers, impedance, and admittance, meeting diverse calibration needs for characteristic parameters in power metering scenarios.

 

Hot Tags: transformer field calibration device, China transformer field calibration device manufacturers, factory, ct pt analyzer, Fully Automatic Transformer Calibration Bench, Transformer Field Calibrator