Product Introduction
MOEORW-WBW03 is an upgraded portable transformer power analyzer with stronger load capacity and wider measurement range. It can complete full-current load test for transformers below 100kVA and 1/3 rated current test for transformers below 250kVA. It integrates automatic calibration, vector display, data storage, on-site printing and harmonic analysis. The humanized operation interface and stable performance make it ideal for field and laboratory transformer testing.
Product Parameter (specification)
|
Working temperature |
−5℃ ~ 40℃ |
|
Relative humidity |
<95% (25℃) |
|
Altitude |
<2500m |
|
Power supply |
220VAC ±15%, 45–55Hz |
|
Voltage range |
10–650V |
|
Current range |
0.2–60A |
|
Frequency range |
45–65Hz |
|
Accuracy |
Voltage / current / frequency: 0.2 class |
|
Power error |
<±0.5% (CosΦ>0.1); ±1.0% (0.02<CosΦ<0.1) |
|
Insulation resistance |
≥100MΩ (input to case) |
|
Withstand voltage |
2kV / 1min (power to case) |
|
Data storage |
500 groups (power-off save) |
|
Parameter preset |
40 groups |
|
Display |
320×240 high-brightness LCD |
Product Feature
- Larger measurement range: current up to 60A, suitable for higher-capacity transformer test.
- Strong load test capability: supports full-current test for 100kVA transformer and extended capacity test via conversion.
- Dual temperature correction: supports temperature coefficient method and national standard formula for accurate loss conversion.
- Automatic wiring judgment: displays vector graph and prompts error immediately to avoid wrong operation.
- User-friendly design: preset parameters, one-key measurement, short cut for printing and data browsing.
- Strong expansibility: compatible with external PT and CT to meet measurement needs of special transformers.
- Stable and durable: anti-interference design, suitable for complex industrial site environment.
Product Application
- Production test and quality control of medium-sized distribution transformers.
- On-site test and acceptance of newly installed transformers.
- Load loss and no-load loss test of power transformers in power stations and substations.
- Energy-saving test and efficiency evaluation of transformers.
- Transformer test and technical analysis in engineering supervision and testing institutions.
Company Qualifications
FAQ
Q: What is the biggest advantage of WBW03 compared with similar models?
A: Larger current range and stronger load capacity, suitable for higher-capacity transformer field test.
Q: How to perform temperature correction for load test?
A: The instrument supports two methods: temperature coefficient method and national standard formula, which can be set in the menu.
Q: What should I do if the current is normal but voltage shows zero?
A: Check voltage wiring, connection terminal and voltage input fuse for damage or poor contact.
Q: Can test data be exported to a computer?
A: Yes, it supports communication with PC to realize data transmission, storage and report generation.
Q: Is it suitable for outdoor field operation?
A: Yes, equipped with widetemperature LCD, but avoid using in rain, humidity and strong electromagnetic environment.