9-phase Microcomputer Relay Protection Tester

Send Inquiry
9-phase Microcomputer Relay Protection Tester
Details
MOEORW-W1900 Adopts integrated touch control design, running independently without external PC. With high-precision linear amplifier, it supports multi-phase output, differential protection and fault simulation. Built-in WiFi and complete software enable automatic report generation, perfect for on-site debugging and calibration of power systems.
Category
Relay Protection Tester
Share to
Description

9-phase Microcomputer Relay Protection Tester

 

Product Introduction

 

  MOEORW-W1900 series microcomputer relay protection tester is a high-performance test device launched by Wuhan Moen Intelligent Electric. It adopts an integrated design with built-in industrial computer and 10.1-inch true-color display, which can work independently without external PC. It supports flexible voltage and current output combination, high-fidelity linear amplifier, rich interfaces, WiFi and GPS time synchronization. The supporting software includes more than 20 test modules, which can realize accurate debugging, calibration and fault simulation of various relay protection devices, and is suitable for power scenarios such as substations and power plants.

 

Product Parameter (specification)

 

The MOEORW -1900 series relay protection testers are available in various standard models and can also be customized to meet customer needs. The technical parameters of all models are the same except for the number of voltage, current, and output phases. See Table 1-1 below for specific models:

model

Voltage output quantity

Current output quantity

MOEORW -1900A

4 phases

3-phase

MOEORW -1900 B (Customizable)

4 phases

6 phases

MOEORW -1900 C

6 phases

6 phases

MOEORW -1900 D

9 phases

9 phases

Table 1-1: MOEORW -1900 Series Model Comparison Table

 

01/

-AC current output

Phase current output per phase (RMS value) 0 ~ 30A Output accuracy 0.1 class

Permissible long-term operating value of phase current (RMS): 10 A

Maximum output power of phase current 450 VA

frequency ) : 0–2000 Hz

Harmonic number 1 to 40 times

02/

-DC current output

Current output 0 to ±10 A per phase Output accuracy class 0.2

Maximum output load voltage 20 V

03/

-AC voltage output

Phase voltage output (RMS ) : 0 ~ 120V Output accuracy class 0.1

Line voltage output (RMS) 0 ~240V

Phase voltage/line voltage output power 80VA / 100VA

Frequency range (fundamental frequency): 0–2000 Hz

Harmonic number 1 to 40 times

04/

-DC voltage output

Phase voltage output amplitude : 0 to ± 160V Output accuracy class 0.2

Line voltage output amplitude 0 ~ ± 320V

Phase voltage/line voltage output power 70VA / 140VA

05/

-Switch quantity

10 pairs of digital inputs

empty contact " 0 ": ≤10kΩ ; " 1 " : ≥20kΩ

Potential contacts connected to " 0 ": 0 ~ +6V ; " 1 ": +11V ~ +250V V

8 pairs of digital outputs

Interruption capacity DC : 250​​ V / 0.3 A ; AC : 250​​​ V / 0.5 A

Response time for standard deployment: ≤1ms; for fast deployment: ≤0.01ms

06/

-Time measurement range

0.1 m s ~ 9999 s Measurement accuracy ≤ 0.1ms

07/

-Volume and weight

364mm × 200mm × 402mm​ 19.8 kg​​ (The weight may vary slightly depending on the model.)

 

 

Product feature and application

 

  1. Flexible output configuration: modular design, optional 4V3A to 9V9A, supporting three-winding transformer differential test and bus transfer test
  2. Integrated structure: built-in industrial computer and touch display, plug and play, easy for mobile test
  3. High-fidelity linear amplifier: no intermediate frequency interference, smooth waveform, high precision
  4. High-performance DSP control: high speed, low distortion, good linearity
  5. Rich interfaces: USB, Ethernet, GPS, built-in WiFi for wireless communication
  6. Powerful software: automatic test, fault replay, report storage, supporting 9-phase differential and 12-phase fast switching test

 

Prodection details

 

The MOEORW-1900 Series Microcomputer-Based Relay Protection Tester is designed for commissioning, calibration, and maintenance of relay protection devices in power systems. It is primarily used in substations, power plants, power maintenance companies, and power research institutions.

Main Application Scenarios

- Conventional protection test:

overcurrent, distance, zero sequence, power direction and other setting verification

01

- Special protection test:

 differential protection, ATS, fast switching, synchronization device logic test

02

- Fault simulation and replay:

support COMTRADE format fault playback

03

- Harmonic and special test:

harmonic restraint, inverse time, power oscillation

04

- On-site mobile test:

portable and suitable for outdoor maintenance

05

 

Company Qualifications

 

Wuhan Moen Intelligent Electric Co., Ltd. is located in Wuhan East Lake High-Tech Development Zone (Optics Valley of China). The company was founded in 1992 (formerly Wuhan High Voltage Research Institute High Voltage Test Equipment Factory), and is one of the earliest manufacturers engaged in high-voltage test in China. The plant covers an area of 28 acres with a construction area of 8,000 square meters, mainly serving power systems, scientific research institutions and equipment manufacturers.

.jpg

.jpg

.jpg

.jpg

.jpg

.jpg

.jpg

 

FAQ

1)In what aspects is the integrated design of the MOEORW-W1900 series microcomputer-based relay protection tester manifested?

Answer: This series of testers adopts an integrated design featuring a built-in industrial control computer and a 10.1-inch true-color LCD display, enabling standalone operation without an external PC. The device integrates multiple interfaces (USB, Ethernet, GPS, Wi-Fi) and power amplifier modules. Its compact structure, small size, and light weight enable immediate operation upon startup, facilitating mobile testing.

2)How does the MOEORW-W1900 series microcomputer-based relay protection tester achieve wireless communication with a PC?

Answer: The tester incorporates a built-in Wi-Fi module supporting two connection modes: Router Mode and Terminal Mode. In Router Mode, the device creates its own hotspot, allowing PCs and other terminals to connect without Ethernet cables. In Terminal Mode, the device can search for and connect to nearby Wi-Fi signals. Once connected, it enables wireless control of the tester's outputs and more flexible data transmission.

3)What formats of fault data files can be imported into the waveform replay function of the MOEORW-W1900 series microprocessor-based relay protection tester?

Answer: The waveform replay function supports importing transient data files in COMTRADE format. This format comprises two core files: CFG (channel configuration file) and DAT (data file). Data can originate from fault recorders or power system transient calculation software (e.g., EMTP). After importing, fault scenarios can be reconstructed and analyze

 

Hot Tags: 9-phase microcomputer relay protection tester, China 9-phase microcomputer relay protection tester manufacturers, factory, Six Phase Relay Protection Tester, 9 phase Microcomputer Relay Protection Tester, relay protection tester, There Phase Relay Protection Tester, 3 phase relay tester, Handheld Optical Digital Relay Protection Tester