Multifunctional Partial Discharge Tester

Send Inquiry
Multifunctional Partial Discharge Tester
Details
MOEORW-WPD530NC is a portable multifunctional partial discharge tester integrating ultrasonic, TEV, UHF and HF detection.
It is used for live inspection, partial discharge location and insulation assessment of switchgears, GIS, transformers and cables, featuring portability, high efficiency, accuracy and stability.
Category
Ultrasonic Partial Discharge Tester
Share to
Description

Product Introduction

 

MOEORW-WPD530NC is an integrated, portable partial discharge detector for live detection of power equipment. It adopts ultrasonic, transient earth voltage (TEV), ultra-high frequency (UHF) and high frequency (HF) technologies, and runs on Linux system with a 6.2-inch touch screen. It can quickly capture partial discharge signals, display PRPD/PRPS and other spectrum diagrams, realize quantitative analysis and defect location, and is widely used in daily inspection and status evaluation of high-voltage cables, transformers, switch cabinets, GIS and other equipment.

 

Product Parameter (specification)

 

Detection Module Parameters

Non-contact Ultrasonic (AA) Center frequency 40kHz±1kHz; Measuring range -10~70dBuV; Gain 40/60/80dB
Contact Ultrasonic (AE) Frequency band 20kHz~200kHz; Measuring range 0~100mV; Gain 20/40/60dB
Transient Earth Voltage (TEV) Frequency band 3MHz~100MHz; Measuring range 0~60dBmV; Rise time 0.4ns
Ultra-high Frequency (UHF) Frequency band 300MHz~1500MHz; Measuring range -80dBm~0dBm; Filter with band-stop/low-pass/high-pass/all-pass
High Frequency (HF) Frequency band 0.3MHz~30MHz; Measuring range 0~70dB; Gain -10~20dB

 

Overall Parameters

Display 6.2-inch TFT touch screen (800*480)
Power Lithium battery, working time ≈5 hours, Type-C charging
Size & Weight 197×125×42mm; Weight: 0.7kg
Working environment -20℃~50℃, humidity 10%~90%
Storage TF card, support U disk export (FAT32)

 

Product Features

 

  • Five-in-one detection: Integrate AA, AE, TEV, UHF, HF detection methods
  • Rich spectrum: PRPD, PRPS, phase linear, four-element diagram for defect analysis
  • Dual-level alarm: Adjustable attention threshold and alarm threshold
  • High sensitivity: Professional antenna and pre-processing circuit design
  • Portable design: Light weight, easy to carry for on-site live detection
  • Data management: Support screenshot, screen recording, storage and U disk export
  • Intelligent function: Automatic gain, intelligent diagnosis, wireless synchronization
  • Strong compatibility: Comply with multiple State Grid technical specifications

 

Product Application

 

  • Live detection of partial discharge of high-voltage switch cabinets
  • Partial discharge test of GIS and gas-insulated equipment
  • Insulation status detection of power transformers and reactors
  • Live detection of high-voltage cables and cable joints
  • Daily inspection and preventive test of power transmission and distribution equipment
  • Defect location and type identification of power equipment insulation faults

 

Company Qualifications

 

  • Comply with Q/GDW 11304 series technical specifications of State Grid
  • Professional R&D and production of power detection equipment
  • Complete quality management system certification
  • Independent intellectual property rights of core technology
  • After-sales service system with national unified customer service hotline
  • Mature application cases in power industry

 

FAQ

 

Q1:How to turn on and off the instrument?

A:Press the power button at the bottom to turn on; press again to turn off. Please charge when the low battery icon appears.

Q2:Can it be charged while working?

A:No. Charging must be done when the instrument is turned off, and the original charger should be used.

Q3:How to export test data?

A:Insert a FAT32 U disk into the top Type-C port, select data in the "Stored Data" interface, and click "Save to U disk".

Q4:What should I do if the signal is disturbed?

A:Test the background noise first, set appropriate threshold and filter, and keep away from strong interference sources.

Q5:Can it be used in thunderstorm weather?

A:No. Measurement is prohibited in thunderstorm, explosive and other dangerous environments.

Q6:How to maintain the instrument?

A:Store in dry and ventilated place; avoid direct sunlight; turn on for about 2 hours every month in humid season to dehumidify.