Marx Generator Circuit Diagram Explained: Working Principle & Stages

Sep 14, 2026

Leave a message

ElectriCore
ElectriCore
Senior electrical engineer with 15 years in substation automation and power quality. Author of technical articles on design codes, troubleshooting, and smart grid. Committed to practical knowledge sharing.

1. What Is a Marx Generator?

A Marx generator is the standard circuit topology behind almost every industrial impulse voltage test system. Named after German engineer Erwin Otto Marx, who proposed it in 1924, it solves a fundamental problem: how do you generate a 400 kV, 800 kV, or 1200 kV pulse when your charging supply only needs to deliver ±100 kV per stage?

The answer is elegant - charge many identical capacitor stages in parallel at a modest voltage, then connect them in series with triggered spark gaps at the moment of discharge, multiplying the output voltage by the number of stages.

This article walks through the Marx circuit diagram stage by stage, explaining what every component does, how single-stage and multi-stage circuits differ, and how the familiar 1.2/50 µs lightning waveform is actually shaped.

 

2. The Core Idea: Parallel Charging, Series Discharge

Think of the Marx generator as a ladder. Each rung is a capacitor, and the side rails are two strings of charging resistors.

During charging:

A DC charging supply (typically 0–100 kV per stage) feeds through high-value charging resistors.

Every capacitor in the ladder charges up to the same voltage - say, +100 kV.

Because the capacitors are effectively in parallel at this point, the supply only has to deliver one stage's voltage, not the full stack voltage.

The spark gaps between stages remain open - air is a good insulator at this voltage.

During discharge:

A trigger pulse fires the first (top-stage) spark gap.

That first gap closing doubles the voltage across the next gap, which overvolts it and causes it to break down next.

This cascades down the ladder - gap after gap fires in nanoseconds.

Now all the capacitors are connected in series. With 4 stages charged to 100 kV each, the load sees 4 × 100 kV = 400 kV across it for a few microseconds.

The total energy stored is simply n × (½·C_stage·V²), where n is the number of stages.

 

3. Annotated Marx Circuit Diagram - Every Component

Below is a walk-through of what you will see in any Marx generator schematic (see Figure 1: impulse voltage generator main circuit diagram):

Component Per-stage role Typical value
Main pulse capacitor (C) Stores energy; one or two per stage 1.5 µF at 100 kV in a 4-stage 30 kJ system
Charging resistor (Rc) Isolates stages during charging; high value so it does not load the pulse Tens of kΩ per stage
Wavefront / damping resistor (Rf) Shapes the rising edge of the impulse; damps parasitic oscillations Selected per load capacitance
Wavetail resistor (Rt) Shapes the decaying tail of the waveform Selected per load capacitance
Firing spark gap (G) Three-electrode, triggered; connects stages in series during discharge φ250 mm sphere gap, motor-adjusted
Insulating column Supports the tower mechanically Epoxy, 2 thick + 3 thin per stage

 The external measurement chain - a weakly damped capacitive divider and a digital recorder - sits across the test object and is not part of the Marx ladder itself.

use Figure 3 from the WGJ43 service manual as the hero schematic of this article, with callout boxes labeling C, Rc, Rf, Rt, G.

 

4. Single-Stage vs Multi-Stage Marx Circuits

Single-stage Marx is a misnomer in the strict sense - a single capacitor charged to the desired voltage and discharged through a gap is just a pulse capacitor, not a Marx circuit. What engineers usually mean by "single stage impulse generator circuit" is a one-rung Marx ladder: one main capacitor, one charging resistor, one firing gap. It tops out around 100–200 kV and is common in teaching labs and small test sets.

Multi-stage Marx is the industrial form:

2 stages / 200 kV: typical for 10 kV-class switchgear and instrument transformer routine tests.

3 stages / 300 kV: entry for 35 kV-class distribution equipment.

4 stages / 400 kV: the workhorse for 35 kV-class distribution transformers, bushings, surge arresters and GIS.

6 stages / 600 kV: 66–110 kV class.

12 stages / 1200 kV and above: EHV / UHV type-test laboratories.

Every additional 100 kV stage adds one rung to the ladder - same topology, more capacitors, more gaps, taller tower.

 

5. How the Wavefront and Wavetail Resistors Shape 1.2/50 µs

The 1.2/50 µs lightning waveform is not produced by the capacitors alone - it is engineered by choosing Rf (front) and Rt (tail).

The front time (1.2 µs) is largely set by how fast the load capacitance charges through the front resistor. Smaller Rf → faster front; too small Rf → parasitic ringing.

The time to half-value (50 µs) is largely set by how slowly the combined capacitor bank discharges through the tail resistor. Larger Rt → longer tail.

For chopped wave (2–6 µs), a separate chopping gap fires into the waveform and truncates it artificially.

For switching impulse (250/2500 µs), the front resistors are retained as damping resistors and larger tail resistors are switched in to slow the waveform down.

In a field-configurable tower, operators swap plug-in resistor sets to move between lightning, switching, oscillating and steep-wave modes - no soldering, no rewiring of the main circuit.

 

6. Why the Charging Supply Stays at Low Voltage

A common question: why not just charge a single capacitor to 400 kV directly?

The answer is insulation. A 400 kV oil-immersed capacitor with terminals rated for that voltage is large, expensive and hard to handle. By contrast, four 100 kV capacitors connected in series during discharge are:

cheaper per joule of stored energy,

easier to ship and install,

modular (add a stage, add 100 kV),

and the charging supply only has to reach 100 kV - a much smaller, safer DC unit.

This is why every modern impulse voltage generator from 100 kV up uses the Marx topology.

 

7. Practical Design Considerations

If you are studying, specifying or buying a Marx-based impulse voltage system, pay attention to:

Stage voltage. Most industrial Marx towers are built at 100 kV per stage. Some compact high-energy designs use 200 kV per stage (e.g. 6 stages = 1200 kV in a shorter tower).

Trigger reliability. Three-electrode gaps with motorized spacing give >99% firing success over thousands of shots; a runaway rate above 2% means unstable test results.

Body inductance. Lower is better. A well-designed 4-stage tower measures under 55 µH.

Divider bandwidth. A weakly damped capacitive divider with ≤100 ns partial response time gives clean waveforms up to the sub-microsecond steep-front tests.

Grounding. Single-point grounding at ≤0.5 Ω is non-negotiable - poor grounding corrupts every measurement.

For a fully configured commercial example, see the 4-stage 400 kV / 30 kV Marx generator built around a Siemens PLC control rack.

 

8. Conclusion

The Marx generator circuit is a masterpiece of 1920s electrical engineering that still defines how high-voltage apparatus is tested today. Parallel charging keeps the charging supply small and safe; series discharge through triggered spark gaps multiplies the voltage; front and tail resistors shape the waveform; and modular stages let you build anything from a 100 kV teaching unit to a 2400 kV UHV type-test system from the same building blocks.