Automatic Transformer Turns Ratio Group Tester

Send Inquiry
Automatic Transformer Turns Ratio Group Tester
Details
This benchtop tester is highly practical and easy to operate. It supports one-time wiring to complete turns ratio, group, polarity, and angle difference testing. It has built-in printing, USB storage, and Bluetooth communication for on-site data output and archiving. With multiple safety protections and stable performance, it is ideal for long-term use in factory inspection, substation handover, and maintenance.
Category
Transformer Turns Ratio Tester
Share to
Description

Product Introduction

 

MOEORW-WBC10 is a bench-top fully automatic transformer turns ratio & group tester independently developed for power transformer production, handover, and maintenance. It fully complies with IEC and national standards, efficiently detecting turn-to-turn short circuit, open circuit, wrong connection, and tap switch faults. With simple operation and stable data, it meets the testing needs of various large, medium and small transformers.

 

Product Parameter (specification)

 

Measuring range

0.9~10000

Accuracy

±(0.1% reading+2 digits) ≤500; ±(0.2% reading+2 digits) 500~3000; ±(0.3% reading+2 digits) >3000

Test voltage

Max 160VAC

Angle resolution

0.1°

Power supply

Built-in lithium battery / AC100-220V

Working temperature

-10℃~50℃

Size

330×280×150mm; Weight:4.7kg

Storage

Built-in 200 data, U-disk Word format export

 

Product Feature

 

  • Three-phase sinusoidal inverter power supply, automatic voltage regulation with soft start/stop
  • Blind test function available without knowing high/low voltage connection mode
  • Support single-phase, three-phase, Z-type transformer, PT/CT test
  • 7-inch color touch screen, clear vector diagram display
  • Reverse connection & short circuit protection, safe and reliable
  • Built-in printer, Bluetooth & RS232 communication
  • Chinese/English interface switchable, real-time clock

 

Product Application

 

Widely used in transformer manufacturers, power supply bureaus, power plants, industrial and mining enterprises, for delivery inspection, handover test and preventive maintenance of distribution transformers, power transformers, voltage transformers and current transformers.

 

Company Qualifications

 

 

FAQ

 

Q: Can it test Z-type transformers?

A: Yes, special Z-type test mode is built-in.

Q: Is data export convenient?

A: Support U-disk export in Word format, directly editable and printable.

Q: Does it have polarity and group judgment?

A: Automatically measure angle difference, judge polarity and connection group.

 

Hot Tags: automatic transformer turns ratio group tester, China automatic transformer turns ratio group tester manufacturers, factory, Frequency Winding Deformation Comprehensive Tester, Special Transformer Turns Ratio Tester, Transformer OLTC On load Voltage Adjustment Switch Characteristics Tester, Transformer On load Switch Tester, Transformer Turns Ratio Group Tester, Transformer Winding Deformation Tester