MOEORW-W4610A12 is a 10A high-speed DC resistance tester for transformers, reactors and inductive coils. It features 7 current gears, 0.5mΩ–100kΩ measuring range, ±(0.2%+2 digits) accuracy, 7-inch touch screen, data storage, printing and USB/RS232 output. With safe discharge alarm, it is ideal for factory, handover and preventive tests.
Category
Transformer DC Winding Resistance Tester
Share to
Description

10A DC Resistance Tester

 

Product Introduction

 

    The measurement of DC resistance is a mandatory test item for semi-finished and finished products during factory inspection, on-site installation, handover tests, and preventive maintenance tests conducted by power departments for inductive coils such as transformers, transformers, reactors and electromagnetic operating mechanisms. It can effectively detect manufacturing defects and potential operational hidden troubles of inductive coils, including material selection problems, poor welding, loose connections, strand missing and wire breakage.

     To meet the demand for rapid DC resistance measurement of inductive coils, our company has developed a DC resistance tester relying on our own technical advantages. Adopting brand-new power supply technology, the instrument features small size, light weight, large output current, wide measuring range, digital display and AC mains power supply.

Controlled by a single-chip microcomputer, the whole machine is equipped with functions such as multiple current gear selection, data processing and display, and discharge indication. With high testing accuracy and simple operation, it enables fast measurement of DC resistance.

 

Product Parameter (specification)

 

1.Output Current: 10A, 5A, 1A, 100mA, 10mA, 1mA, Auto

2.Measuring Range:0.5mΩ~1.6Ω (10A gear)

                                20mΩ~3.2Ω (5A gear)

                                100mΩ~16Ω (1A gear)

                                16Ω~100Ω (100mA gear)

                                100Ω~2kΩ (10mA gear)

                                2kΩ~100kΩ (1mA gear)

3.Accuracy: ±(0.2% + 2 digits)

4.Resolution: 0.1μΩ

5.Operating Temperature: -20~40℃

6.Ambient Humidity: ≤80%RH, no condensation

7.Altitude: ≤1000m

8.Power Supply: AC220V±10%, 50Hz±1Hz

9.Overall Dimension: 323×275×135mm

10.Weight: 4.0kg

 

 

Product feature and application

 

  • The instrument features large output current and light weight.
  • It provides 7 selectable output current gears, with a maximum output current up to 10A.
  • Built with a complete protection circuit for higher operational reliability; it is equipped with an acoustic discharge alarm to avoid misoperation.
  • Wide measurement range from 0.5mΩ to 100kΩ. The temperature of the test object can be set manually, and the instrument automatically calculates the converted resistance value.
  • It can calculate the three-phase unbalance rate, enabling quick and intuitive evaluation of transformer operation stability.
  • Equipped with a 7-inch color touch screen at 800×480 pixel resolution, supporting Chinese/English menu switching and real-time printing of test results.
  • Comes with an RS232 interface for transmitting test data to the background system.
  • Supports powerful data storage, with a capacity of up to 1000 test records.
  • Built-in USB interface allows saving test data to a USB flash drive.
  • Comprehensive parameter settings are available, including transformer test winding, tap position, test phase, test object temperature, conversion temperature, winding material and other options.

 

Prodection details

 

Semi-finished and finished product delivery tests in manufacturing

On-site installation and handover tests

 Preventive tests by power departments

 

Company Qualifications

 

 

FAQ

1)What is the maximum output current of the DC Resistance Tester, and how many current ranges are available?

The maximum output current is 10A. There are 7 current ranges in total: 10A, 5A, 1A, 100mA, 10mA, 1mA, and Auto.

2)Why can't the test leads be removed immediately after testing with the DC Resistance Tester?

The instrument retains residual charge when testing inductive loads. You must wait until the discharge alarm stops and discharging is fully completed before turning off the power and removing the test leads, to avoid electric shock or equipment damage.

3)How many test records can the DC Resistance Tester store, and how to export the data?

It can store up to 1000 test records. Data can be exported to a USB flash drive via the USB port, or transmitted to a host computer through the RS232 port.

 

Hot Tags: 10a dc resistance tester, China 10a dc resistance tester manufacturers, factory, DC Resistance Fast Tester, High Precision DC Resistance Tester, DC Low Resistance Tester, transformer dc winding resistance tester, 20A DC Resistance Tester, Handheld 10A DC Resistance Tester