Three-Phase Microprocessor-Based Relay Protection Tester

Send Inquiry
Three-Phase Microprocessor-Based Relay Protection Tester
Details
MOEORW-W1900A multi-channel relay tester supports up to 9-phase signal output and COMTRADE fault playback.
Equipped with GPS synchronous function, it perfectly serves large power plants and research labs for complex protection characteristic analysis.
Automated test workflows greatly reduce labor costs of high-standard type tests.
Category
Relay Protection Tester
Share to
Description

Product Overview

 

The MOEORW-W1900A is a multi-channel modular relay protection tester, available in multiple output configurations such as 4U3A, 6U6A and 9U9A. It adopts embedded industrial control system and high-performance DSP, with 10.1-inch TFT LCD and trackball operation. This series of products supports rich test functions including fault recurrence, impedance characteristic test and out-of-step oscillation simulation, and is suitable for high-standard testing of complex protection equipment in large substations, power plants and power research institutions.

 

Technical Parameters

 

Analog Output Parameters

Category

Item

Parameter

Accuracy

AC Current

Single-phase (RMS)

0 ~ 30 A

0.1 Class

 

Long-term allowable current

≤ 10 A

-

 

Max output power per phase

450 VA

-

 

Fundamental frequency range

0 ~ 2000 Hz

-

 

Maximum harmonic order

1 ~ 40

-

DC Current

Single-phase

0 ~ ±10 A

0.2 Class

 

Max load voltage

20 V

-

AC Voltage

Single-phase (RMS)

0 ~ 120 V

0.1 Class

 

Line voltage (RMS)

0 ~ 240 V

-

 

Phase / Line output power

80 VA / 100 VA

-

DC Voltage

Single amplitude

0 ~ ±160 V

0.2 Class

 

Line amplitude

0 ~ ±320 V

 
 

Phase / Line output power

70 VA / 140 VA

-

 

Switching Quantity Parameters

Item

Specification

Binary Input

10 channels; Dry contact: ≤10 kΩ (Off), ≥20 kΩ (On); Potential contact: 0~6 V (Off), 11~250 V (On)

Binary Output

8 pairs (4 conventional + 4 high-speed); Rated load: DC/AC 250 V, 0.3 A / 0.5 A

Binary Output Response Time

Conventional: ≤1 ms; High-speed: ≤0.01 ms

 

Timing & Physical Parameters

Item

Specification

Timing Measurement Range

0.1 ms ~ 9999 s

Timing Accuracy

≤ 0.1 ms

Dimension

364 mm × 200 mm × 402 mm

Net Weight

19.8 kg

 

Main Features

 

Hardware & Structural Characteristics
1.Modular Multi-channel Design: Supports multiple output combinations from 4U3A to 9U9A, which can be selected according to test requirements, adapting to single-phase, three-phase and three-winding transformer differential tests.
2.High-performance Control Core: Equipped with 32-bit DSP and high-precision D/A converter, the signal sampling and output rate are high, which can restore complex transient fault waveforms.
3.Integrated Operation Panel: 10.1-inch true-color LCD, trackball and dedicated keypad are integrated on the front panel for convenient standalone operation.
4.Diversified Communication: Dual RJ45 network ports, WiFi, GPS antenna interface and multiple USB ports are configured to support wired/wireless communication and GPS synchronous test.
5.Enhanced Power Amplifier: Adopts high-fidelity linear power module with complete over-current, over-voltage and short-circuit protection, ensuring stable long-term operation.
 

Core Performance
1.Ultra-wide Frequency & Harmonic Range: The fundamental frequency reaches up to 2000 Hz and supports 40 orders of harmonic output, meeting the test requirements of high-frequency equipment and harmonic protection.
2.High Measurement Accuracy: The overall accuracy of AC and DC signals is up to 0.1/0.2 class, which satisfies the laboratory-level precision test standards.
3.High-speed Binary Output: The high-speed binary output response time is less than 0.01 ms, applicable to the test of high-speed protection components.
4.Flexible Fault Simulation: Supports various fault types such as phase-to-phase short circuit, grounding fault and conversion fault, and can simulate complex operating conditions such as power oscillation.
 

Functional Advantages & Application Value
1.Comprehensive Test Modules: Built-in 20+ professional modules including fault recurrence, impedance characteristic, out-of-step oscillation, backup power auto-switching and fast switch, covering all types of power protection tests.
2.COMTRADE File Support: The fault recurrence module can import standard COMTRADE format fault recording files for waveform playback and fault reproduction analysis.
3.Automatic Test & Report: One-click automatic test flow, real-time data recording, and diversified report generation and export functions improve test efficiency.
4.GPS Synchronization: Built-in GPS module realizes synchronous test of multiple devices, which is suitable for double-ended protection test of long-distance transmission lines.
5.Rich Customization: The software supports function customization and module expansion, which can be tailored according to special test requirements of users.

 

Application Fields

 

1.Large Substations: Daily maintenance, acceptance and fault analysis of full set of line, busbar and transformer protections.
2.Power Plants: Comprehensive test of generator unit protection, plant power supply switching and related auxiliary protections.
3.Power Research Institutes: Performance research, simulation test and new product development of protection devices.
4.High-voltage Engineering Commissioning: On-site test of protection systems for long-distance transmission lines and large-scale power transformation projects.
5.Professional Detection Institutions: Third-party calibration and type test of relay protection equipment.

 

Working Principle

 

The MOEORW-W1900A takes the embedded industrial control unit as the main control unit and DSP as the signal output core:
1.The upper computer (industrial control unit) receives the test parameters set by the user, and sends the command to the DSP unit.
2.The DSP adopts 32-bit double-precision algorithm to generate standard digital waveforms, which are converted to analog signals via high-resolution D/A converter.
3.The analog signals are amplified by the linear power amplifier and output from the voltage/current terminals to the tested protection device.
4.The binary input channel collects the action signals of the protection device and feeds them back to the main control unit for timing and data recording.
5.The binary output channel outputs control signals according to the test logic to cooperate with the simulation of switch actions.
6.The whole system realizes closed-loop control of parameter setting, signal output, signal acquisition and data analysis.

 

Standard Accessories

 

1.Main power cord × 1
2.Full set of voltage and current test cables
3.Binary input/output connecting wires × 1 set
4.GPS antenna (optional)
5.Network cable × 2
6.User manual and software CD × 1 set

 

FAQ

 

Q: Failed to import COMTRADE files for fault recurrence?

A: Confirm that CFG, DAT files are complete and stored in the same directory; check the file format compatibility.

Q: GPS cannot be positioned?

A: Check the GPS antenna connection and ensure the antenna is placed in an open area with good signal.

Q: The high-speed binary output fails to act?

A: Verify the wiring of high-speed output terminals and check the load capacity.

Q: The network connection is unstable?

A: Reconnect the network cable or switch to WiFi mode; check the IP address configuration.

Q: The device restarts randomly during operation?

A: Check whether the input power is unstable or the heat dissipation is blocked.

 

Hot Tags: three-phase microprocessor-based relay protection tester, China three-phase microprocessor-based relay protection tester manufacturers, factory, 6 phase relay test set, 6 phase relay tester, 9 phase Microcomputer Relay Protection Tester, Six Phase Secondary Current Injection, There Phase Relay Protection Tester, Three Phase Secondary Current Injection Relay Test Set