Product Introduction
MOEORW-WTEV is a partial discharge detection sensor based on the Transient Earth Voltage (TEV) principle, specially used for insulation status monitoring of metal-enclosed switchgear. When partial discharge occurs inside the switchgear, the generated electromagnetic wave induces a weak transient voltage on the metal cabinet surface, which is captured by this sensor through capacitive coupling.
The sensor adopts a disc-shaped structure with a strong magnet on the back, which can be directly adsorbed on the switchgear shell without any installation tools. The internal circuit is fully encapsulated with epoxy resin, providing excellent moisture-proof, dust-proof and anti-vibration performance. It outputs standard analog signals and can be connected to various PD monitoring devices for online monitoring and regular inspection of switchgear.
Product Parameter (specification)
|
Parameter |
Value |
|
Principle |
Capacitive Voltage Divider |
|
Type |
Disc Magnetic Mount |
|
Bandwidth |
3MHz-100MHz |
|
Housing Material |
Aluminum Alloy |
|
Internal Process |
Epoxy Resin Potting |
|
Interface |
Q9 (BNC) Connector |
|
Operating Temperature |
-40℃~+85℃ |
|
Installation |
Magnetic (Cabinet Surface) |
Product Features and Applications
- Capacitive voltage divider principle, accurate detection of transient earth voltage signals
- Disc-shaped adsorption design, small footprint, flexible layout on any switchgear position
- Aluminum housing + epoxy potting, strong anti-interference, long service life
- 3MHz-100MHz wide bandwidth, covers common PD signal frequencies in switchgear
- Simple and reliable structure, cost-effective, suitable for large-scale deployment
Prodection details
- Large-scale switchgear batch deployment monitoring
- Low-cost distribution network insulation detection
- Industrial enterprise power distribution room daily inspection
- Community power distribution cabinet status monitoring
- Temporary power equipment acceptance testing
Company Qualifications
FAQ
Q1: What is the working principle of the TEV sensor?
A: It uses capacitive coupling to detect transient earth voltage signals generated on the metal cabinet surface when internal partial discharge occurs.
Q2: Does it affect the normal operation of the switchgear?
A: No. The non-intrusive magnetic installation does not require drilling or wiring modification, and has no impact on equipment operation.
Q3: What is the service life of the sensor?
A: With epoxy resin potting and aluminum alloy housing, the service life is more than 10 years under normal working conditions.
Q4: Can it be used on high-voltage equipment above 35kV?
A: It is mainly designed for 10kV-35kV metal-enclosed switchgear. For higher voltage equipment, we recommend using the UHF sensor.
Hot Tags: tev disc magnetic pd sensor, China tev disc magnetic pd sensor manufacturers, factory