6-35kV Cable PD Test System

Send Inquiry
6-35kV Cable PD Test System
Details
Integrated partial discharge test system for 6–35kV cables. Supports high-precision detection and precise location, equipped with automatic analysis and safety protection, widely used in cable preventive tests and fault diagnosis.
Category
Oscillatory Wave Partial Discharge Tester
Share to
Description

Product Introduction

 

The MOEORW-WPO51 is a compact, integrated partial discharge test system specially developed for onsite diagnosis of 6kV–35kV medium and low voltage power cables. Based on the damped AC oscillation wave (OWTS) principle, the device generates 20Hz–850Hz oscillating voltage to stimulate insulation defects and capture weak partial discharge signals.

 

The system consists of a lightweight highvoltage unit and a portable control terminal, supporting both wired and wireless communication. With the OWTS V2.2 intelligent software, it realizes onestop operation including ranging, calibration, pressurization, data analysis and automatic report generation. It provides safe, nondestructive and highprecision detection for cable handover tests, preventive tests and fault location.

 

Product Parameter (specification)

 

Maximum Output Voltage ±30kV
Inductance Range 0.7H–1.1H Optional
Partial Discharge Measurement Range 10pC–200nC
Measurement Accuracy ±0.1pC (14-bit Sampling)
Oscillation Frequency 20Hz–850Hz
Signal Bandwidth 100kHz–50MHz Auto/Manual
Positioning Accuracy ±0.1m
Positioning Error ≤1% Of Cable Length
Dielectric Loss Range 0.1%–5.0%
Operating Temperature -20℃~60℃
Dimensions Φ650mm, H600mm
Weight 50kg

 

Product Feature

 

  • Lightweight and portable structure, easy for on-site transportation and operation.
  • Ultra-high sensitivity PD detection, capable of identifying micro-defects down to 10pC.
  • TDR-based precise fault location, supporting automatic and manual analysis.
  • Dual communication modes: wired Ethernet and wireless WIFI for stable control.
  • Built-in safety mechanism: emergency stop, high-voltage interlock and reliable grounding.
  • Automatic pressurization in line with DL/T 1576 standard, reducing manual operation.
  • One-key report generation with complete spectrum including Q-L, N-L and PRPD.

 

Product Application

 

  • Handover test for newly laid 6–35kV power cables.
  • Routine preventive test for in-service cable lines.
  • Installation quality inspection of cable terminals and intermediate joints.
  • Insulation status evaluation for aged cables.
  • Rapid positioning of partial discharge fault points.
  • Suitable for plastic, rubber and oil-paper insulated cables.

 

Company Qualifications

 

 

FAQ

 

Q1: What voltage level cables does PO51 apply to?

A: It is designed for 6kV–35kV medium and low voltage power cables.

Q2: Is calibration necessary before testing?

A: Yes, TDR ranging and standard PD calibration ensure measurement accuracy.

Q3: Can this equipment be used outdoors?

A: It can work outdoors in dry conditions; avoid humid or rainy environments.

Q4: Does the test cause damage to cable insulation?

A: No, it uses nondestructive oscillation wave technology.

Q5: What kind of training is required for operators?

A: Basic high-voltage safety training and equipment operation training are recommended.

 

Hot Tags: 6-35kv cable pd test system, China 6-35kv cable pd test system manufacturers, factory