Product Introduction
MOEORW‑W1352 is a professional non‑disconnection grounding resistance tester designed for transmission tower, self‑locking tower and substation. It adopts innovative four‑clamp wireless measurement technology, which can realize online measurement without power cut and wire disconnection. The instrument has high‑definition color screen, built‑in printer and Bluetooth communication, which is convenient for on‑site operation and data output. IP65 waterproof and shockproof structure ensures stable performance in harsh outdoor environment.
Product Parameter (specification)
1. Baseline conditions and operating conditions
|
Impact |
Baseline conditions |
Working conditions |
Remark |
|
Ambient temperature |
23℃±1℃ |
-10℃~40℃ |
---- |
|
Ambient humidity |
40%~60% |
<80% |
---- |
|
Instrument operating voltage |
DC 7.8V±0.1V |
DC 7.8V±0.6V |
---- |
|
Auxiliary grounding resistance value |
<100Ω |
<10kΩ |
---- |
|
Interference voltage |
none |
<20V |
---- |
|
Interference current |
none |
<1A (50Hz) |
---- |
|
Electrode spacing during R measurement |
a>5d |
a>5d |
---- |
|
Electrode spacing when measuring ρ |
a>20h |
a>20h |
---- |
2. General Specifications
|
Function |
Four-clamp method for measuring tower grounding resistance; two-, three-, and four-wire method for measuring grounding resistance and soil resistivity; AC current; grounding voltage. |
|
power supply |
DC 7.4V , 5200mAh rechargeable lithium battery, fully charged to approximately 8.4V. |
|
range |
4-clamp method for measuring grounding resistance: 200Ω |
|
Grounding resistance: 0.00Ω~20.00kΩ |
|
|
Soil resistivity: 0.00Ωm ~ 9000kΩm |
|
|
Measurement method |
4-clamp method, precision 4-wire method, 3-wire method measurement, and simple 2-wire method measurement of grounding resistance, AC current, and grounding voltage. |
|
Measurement methods |
Tower grounding resistance: 4-clamp method Grounding resistance: Rated current polarity changing method, measured current 55mA Max Soil resistivity: Four-electrode method (Winner method) Alternating current: clamp CT, RMS acquisition Grounding voltage: voltage divider, RMS value acquisition |
|
Current clamp diameter |
Φ68mm |
|
Test frequency |
128Hz/111Hz/105Hz/94Hz (AFC) |
|
Short-circuit test current |
AC 55mA max |
|
Open circuit test voltage |
AC 15V max |
|
Test voltage waveform |
sine wave |
|
Electrode spacing range |
The setting can be from 1m to 100m. |
|
Shift |
4-clamp method for measuring grounding resistance: 200Ω fully automatic range switching |
|
Grounding resistance: 0.00Ω~20.00kΩ Fully automatic range shifting |
|
|
Soil resistivity: 0.00Ωm~9000kΩm Fully automatic gear shifting |
|
|
AC current (single CT): 1.00mA~500A fully automatic range shifting |
|
|
Grounding voltage: 0.0V~200.0V |
|
|
Display mode |
7-inch color screen |
|
Measurement indication |
LED flashing during measurement |
|
LCD size |
151mm×83mm |
|
Instrument Dimensions |
Height, Width, and Thickness: 355mm × 272mm × 164mm |
|
Standard test line |
4 strips: one 20m red strip, one 20m black strip, one 10m yellow strip, and one 10m green strip. |
|
Simple test line |
Two strips: one red 1.6m strip and one black 1.6m strip. |
|
auxiliary grounding rod |
4 pieces: φ 9 mm × 230 mm (approximately 935g) |
|
Measurement time |
Grounding resistance, soil resistivity: approximately 30 seconds/time |
|
Number of measurements |
More than 5000 short-circuit tests (test once, pause for 30 seconds, then test again). |
|
Line voltage |
Measurement below AC 600V |
|
Communication interface |
It features a USB interface, software monitoring, and data storage that can be uploaded to a computer, saved, and printed. |
|
printer |
Built-in |
|
Data storage |
Group 100, "001/100" storage indicator, displaying "100/100" indicates that storage is full. |
|
Overflow display |
The "OL" symbol indicates over-range overflow. |
|
Auxiliary grounding test |
It has an auxiliary grounding resistance value testing function, ranging from 0.00KΩ to 20kΩ (100R+rC<20kΩ, 100R+rP<20kΩ). |
|
Alarm function |
|
|
Automatic shutdown |
Automatic shutdown 30 minutes after powering on. |
|
Battery voltage |
When the battery voltage drops to approximately DC 7.2V ± 0.1V, the low battery symbol " |
|
Operating current |
Standby: Approximately 400mA |
|
Measurement: Approximately 550mA |
|
|
quality |
Instrument: Approximately 2765 g (including battery) |
|
Current clamp: Approximately 500 g x 4 pieces |
|
|
Total weight: Approximately 9000 g (including accessories) |
|
|
Operating temperature and humidity |
-10℃~40℃; below 80% RH |
|
Storage temperature and humidity |
-20℃~60℃; below 70% RH |
|
Overload protection |
Measure grounding resistance: AC 280V/3 seconds between each port of C(H)-E and P(S)-ES. |
|
Protection level |
IP65 (with lid closed) |
|
Insulation resistance |
20MΩ or higher (500V between circuit and casing) |
|
Pressure resistance |
AC 3700V/rms (between circuit and casing) |
|
Electromagnetic properties |
IEC61326(EMC) |
|
Suitable for safety regulations |
IEC61010-1 (CAT III 300V, CAT IV 150V, pollution level 2); IEC61010-031; IEC61557-1 (grounding resistance); IEC61557-5 (soil resistivity); JJG 366-2004. |
3. Basic errors and performance indicators under reference conditions
|
Measurement function |
Measurement range |
accuracy |
Resolution |
|
Grounding resistance ( R ) (4-clamp method) |
0.10Ω~20.00Ω |
±10%rdg±5dgt |
0.01Ω |
|
20.0Ω~200.0Ω |
0.1Ω |
||
|
Grounding resistance ( R ) |
0.10Ω~20.00Ω |
±2%rdg±3dgt |
0.01Ω |
|
20.0Ω~200.0Ω |
±2%rdg±3dgt |
0.1Ω |
|
|
200Ω~2000Ω |
±2%rdg±3dgt |
1Ω |
|
|
2.00kΩ~20.00kΩ |
±4%rdg±3dgt |
10Ω |
|
|
Soil resistivity ( ρ ) |
0.00Ωm~99.99Ωm |
(ρ=2πaR a :1 m~100m; π=3.14) |
0.01Ωm |
|
100.0Ωm~999.9Ωm |
0.1Ωm |
||
|
1000Ωm~9999Ωm |
1Ωm |
||
|
10.00kΩm~99.99kΩm |
(ρ=2πaR a :1 m~100m; π=3.14) |
10Ωm |
|
|
100.0 kΩm~999.9 kΩm |
100Ωm |
||
|
1000kΩm~9000kΩm |
1kΩm |
||
|
Alternating current (A~) |
1.00mA~50.00mA |
±2%rdg±3dgt |
0.01mA |
|
0.50A~5.000A |
±2%rdg±3dgt |
0.001A |
|
|
5.0A~500.0A |
±3%rdg±3dgt |
0.1A |
|
|
Grounding voltage (V~) |
0.0V ~ 200.0V |
±2%rdg±3dgt |
0.1V |
Note 1. Additional error when rC max or rP max ≤ ±3%rdg±5dgt.
(rC max: 4kΩ+100R<20kΩ; rP max: 4kΩ+100R<20kΩ)
Additional error at 5V interference voltage ≤ ±5%rdg±5dgt.
Warning: Do not perform voltage measurements while the instrument is charging, connected to a computer, or powered externally.
Product features and applications
- Exclusive 4‑clamp wireless measurement for tower grounding resistance
- Support 2‑wire, 3‑wire, 4‑wire standard measurement and soil resistivity test
- 7‑inch color display, built‑in thermal printer for on‑site report printing
- Bluetooth + USB communication, mobile APP remote control and data viewing
- φ68mm large clamp, 5200mAh large capacity battery, long working time
- IP65 protection grade, waterproof, dustproof and anti‑fall for outdoor use
Prodection details
- Transmission line: tower, concrete pole, self‑locking tower non‑disconnection test
- Power grid: substation grounding grid, distribution room precision grounding detection
- Engineering survey: soil resistivity test for outdoor grounding system design
- Outdoor engineering: high altitude, mountain, no power supply environment measurement
- Emergency repair: power fault rush repair, lightning protection hidden danger detection
- High‑voltage engineering: online monitoring of grounding voltage and leakage current
Company Qualifications
FAQ
1.Are you a manufacturer?
We are a direct factory engaged in R&D, production and sales of grounding testing equipment.
2.How long is the after‑sales warranty?
Standard 1‑year warranty, and we provide lifelong technical support and maintenance.
3.Can it test towers without disconnection?
Yes, 4‑clamp wireless technology realizes online measurement without disconnection and outage.
4.Does it support field printing?
Equipped with built‑in printer, you can print test results directly on site.
5.What languages does the system support?
Default English version, other languages can be customized according to your demand.
Hot Tags: ground resistance tester for self-locking tower, China ground resistance tester for self-locking tower manufacturers, factory, Portable Digital Earth Resistance Tester, Handheld Earth Continuity Resistance Tester, Soil Resistivity Ground Resistance Tester, 20A Portable Ground Continuity Resistance Tester, Handheld Earth Resistance Meter, AC/DC Earth Resistance Tester
When the measured value exceeds the alarm setting value, Alarm symbol prompt