108kVA-108kV Series Resonance Test Device

Send Inquiry
108kVA-108kV Series Resonance Test Device
Details
This set brings you safer and more efficient AC withstand voltage tests for 35kV power transformers and 10kV long cables. Its lightweight design and fully automatic operation save you heavy handling and complicated wiring; pure sine wave output avoids false breakdown and damage to joints, helping you pass handover tests smoothly and reduce rework.
Category
AC Resonant Test System
Share to
Description

108kva-108kv series resonance test device

 

Product Introduction

 

    MOEORW-WXB68-108kVA/108kV frequency conversion series resonance test set is specially designed for AC withstand voltage tests of 35kV and below power main transformers, busbars, switches and other electrical equipment. It adopts a modular reactor design, which can flexibly adapt to high-voltage small-current and low-voltage large-current test scenarios, and is an ideal high-voltage test equipment for power departments and maintenance units.

 

Product Parameter 

 

  1. Rated capacity: 108kVA
  2. Rated output voltage: 27kV/54kV/108kV
  3. Input power: Single-phase 380V
  4. Frequency adjustment range: 20Hz~300Hz
  5. Waveform distortion rate: <1.0%
  6. System measurement accuracy: 1.5%
  7. Quality factor: Q>50
  8. Continuous working time: 15 minutes at rated load

 

Product feature and application

 

  1. Adopt DSP digital platform, support function expansion and human-computer interaction upgrade
  2. Equipped with over-voltage, over-current, zero-start, flashover protection, record flashover voltage
  3. Three working modes: full-automatic, manual, automatic tuning + manual voltage boost
  4. Single piece weight ≤40kg, easy to carry and on-site use
  5. Automatic frequency sweep with adjustable start/end frequency and direction, display resonance curve in real time

 

 

Prodection details

 

  1. 10kV/35kV cross-linked cable AC withstand voltage test
  2. 35kV and below power transformer AC withstand voltage test
  3. 35kV substation switch, busbar and other equipment AC withstand voltage test

 

FAQ

1)Why can't the resonance point be found during automatic tuning?

Answer: Check whether the grounding is reliable, the wiring is correct, and whether the reactor, divider and other components are open circuit.

 

Hot Tags: 108kva-108kv series resonance test device, China 108kva-108kv series resonance test device manufacturers, factory, 108kVA 108kV Series Resonance Test Device, Series Resonant Test Set, high voltage test system, Hv Resonant Test System, 54kVA 54kV Series Resonance Test Device, Lightweight Variable Frequency Resonant Systems