Three-Phase Meter Field Calibrator

Send Inquiry
Three-Phase Meter Field Calibrator
Details
MEDX-W3Y Multifunctional Three-Phase Meter Field Calibrator enables simultaneous precise measurement and calculation of full-wave, fundamental, and harmonic components. Its cumulative energy function allows calibration of meters without energy pulse output. High-safety design.
Category
Electric Energy Test Equipment
Share to
Description

Multifunctional Three-Phase Meter Field Calibrator

 

Product Introduction

 

The MEDX-W3Y Multifunctional Three-Phase Meter Field Calibrator leverages the latest technological advancements to deliver unprecedented functionality. It enables simultaneous, precise measurement and calculation of full-wave, fundamental, and harmonic components.

Its efficient touch interface allows clear selection of your desired functions even within complex menus. For basic testing, operation remains as straightforward as previous instruments. For harmonic analysis, we test all harmonic parameters.

 

Product Parameter (specification)

 

Voltage

Guarantee error range

25-600V

Start measurement value

0.5V

Rated value

440V

Error level

±0.05%

Current

terminal

Rated Ie

5A

scope

0.025A-12A

clamp meter

Rated Ie

5A, 100A, 500A, 1000A

scope

0.5% Ie - 2.4 Ie

Starting current

0.02%Ie

Input frequency range

45-65Hz

Frequency measurement error

±0.0 1Hz

Phase measurement range

-180°- 180°

Maximum phase error

± 0.1 °

Harmonic percentage, harmonic electrical parameters, number of harmonic energy measurements

2-51 times

Pulse constant

(Note: Ie -- rated current)

low frequency output

(Three gears)

5A

3600P, 36000P, 360000P/kWh (kvarh, kVAh)

other

3600P, 36000P, 360000P *(5/Ie) P/ k Wh

(kvarh, kVAh)

Internal high frequency

5A

1.8 x 10⁹ P / kWh

Other current settings

1.8x10⁹​ * ( 5/Ie) P/ kWh

Maximum pulse input frequency

50kHz

5A terminal

Full-wave fundamental kWh, P, U, I

±0.05%

Full wave fundamental wave Kvarh, Q, VA, VAh

±0.2%

Harmonics U, I, P, Q, S

±0.2%H (H=1+0.01k K=2-51)

5A clamp meter

Full-wave fundamental kWh, P, U, I

±0.2%

Full wave fundamental wave Kvarh, Q, VA, VAh

± 0.2 %

Harmonics U, I, P, Q, S

±0.5% H (H=1+0.01k K=2-51)

Self-test current cyclic output current

0.05A,0.1A,0.25A,0.5A,1A,2.5A,5A

Self-checking errors (linearity and angle difference)

± 0.1 %

High Current Clamp

Full-wave fundamental kWh, P, U, I

±0.5%

Full wave fundamental wave Kvarh, Q, VA, VAh

±0.5%

Harmonics U, I, P, Q, S

±1.0% H (H=1+0.01k K=2-51)

other

Transformer ratio measurement

± 0.5 %

Voltage effect

< ±0.01%

Frequency influence

< ±0.01%

Temperature effect

< ± 0.005 % / ℃

24-hour deterioration

< ±0.01%

Harmonic effects

< ±0.01%

rechargeable batteries

11.1V 3000mAh

Withstand voltage (voltage and current measurement and between power supply and low voltage terminals)

4.0 kV

Electrical Fast Transient Burst

4.0 kV

surge

4.0kV (common mode), 2.0kV (differential mode)

Startup stability time

<3 minutes

Ambient temperature

-25℃ to +45℃

relative humidity

40%-95%

working power supply

AC 55V - 600V

achievement Consumption

< 9W

External dimensions

275mm * 196mm * 78mm​

Heavy quantity

< 1.5 kg​

 

Product feature and application

 

  • Simultaneously calculate all parameters for full-wave, fundamental, and harmonic components On the verification interface, simultaneously display in real-time the full-wave fundamental's U, I, P, Q, VA, and phase angle, along with the harmonic's composite U, I, P, Q, VA and percentage, positive-sequence, negative-sequence, and zero-sequence content of U and I, harmonic PH+, PH-, PH+/P base%, PH-/P base%, total wave PF, fundamental PF, and harmonic PF
  • Calibration modes include seven types: total wave active, total wave reactive, fundamental active, fundamental reactive, fundamental apparent, total wave apparent, and harmonic active Can verify the active energy accuracy of full-wave meters, fundamental-wave meters, and harmonic meters, as well as the reactive energy accuracy of full-wave meters and fundamental-wave meters Can also verify the accuracy of apparent energy meters
  • Can select any single or multiple harmonics to calculate the composite U, I, P, Q, VA, and percentage, as well as harmonic active energy
  • Simultaneously analyzes the content and measured values of U, I, P, Q, and VA for each harmonic of all three phases Displays the st harmonic + PH, harmonic - PH, and percentage relative to the fundamental wave to determine the impact of positive and negative harmonic active energy on metering
  • Total reactive power is the algebraic sum of fundamental and harmonic reactive components This eliminates measurement errors under harmonics caused by the traditional -degree phase-shift method Select harmonic orders based on the meter's measurement bandwidth
  • Simultaneously detects two test pulses with fully independent constants, operating modes, and pulse counts
  • At times overload, all measurement points guarantee % accuracy, ensuring measurement specifications when CT secondary rated current is A Measurement specifications guaranteed across times current range;
  • Measurement specifications guaranteed across times current range, with , times current display range Minimum start-up current of mA High-supply high-metering capability; wiring can be identified even under no-load conditions
  • Energy accumulation function verifies meters without pulse output
  • Displays vector diagrams, identifies three-wire and four-wire wiring errors, and detects CT secondary cross-wiring
  • Features a -inch : industrial-grade TFT widescreen color touchscreen Each instrument function is displayed on a single screen, allowing users to view all parameters for every function without scrolling This provides clear visibility during operation
  • Without connecting voltage or current signals, the instrument can simulate various field wiring configurations in an office environment, generating corresponding wiring results and correction factors This feature serves as a training tool for wiring verification, enhancing field personnel's troubleshooting skills
  • The instrument generates actual current signals ranging from A to A, which can be applied to the A clamp to measure its measurement error This resolves the issue of error drift in A clamps after prolonged use It allows real-time monitoring of the clamp's closure status, alerting personnel to clean the jaws When replacing the A clamp, the measurement error can be corrected to Class accuracy
  • Automatic Energy Meter Number Entry (Optional Feature)
  • Supports barcode scanners for automatic entry of energy meter codes
  • Utilizes or infrared photoelectric heads to read the active and reactive energy readings for off-peak, peak, normal, and total periods from multifunctional electricity meters, as well as reading constants and time calibration Supports national standards DL protocols DL- and DL- (Optional feature)
  • Built-in GB electronic disk
  • Supports -inch on-site printer, battery-powered, directly converting color screen images to monochrome for printing
  • Includes A, A, A, A clamp meters for direct measurement of low-voltage current transformer ratio and ratio error
  • Displays waveforms for A, B, and C phase voltages and currents
  • Operating power input range: V-V Industrial socket rated voltage for three-phase input is V Industrial-grade switch selects between external mains power and three-phase voltage as operating power source
  • All field-required input parameters and downloadable data can be freely defined by the user Supports downloading data for up to users
  • Current screen can be saved to a USB flash drive
  • Features temperature and humidity measurement (requires temperature/humidity sensor)
  • Equipped with a USB port for connecting a USB flash drive, creating an extended storage space for convenient data copying

 

Prodection details

 

Field Inspection of Power Systems:

The three-phase electricity meter field calibrator is specifically designed for on-site verification of operational errors and fault detection in grid metering instruments within power systems.

01

Calibrating Meter Errors:

Enables on-site verification of electricity meter errors, inspection of correct wiring in metering devices, and detection of current transformer ratio and polarity for metering purposes.

02

Power Quality Measurement:

Features the capability to measure user power quality parameters, including voltage harmonics, current harmonics, voltage unbalance, and total harmonic distortion (THD).

03

Detection of Electricity Theft:

Through testing, it can determine whether users engage in electricity theft, whether metering accuracy meets national standards, whether users cause harmonic pollution affecting grid quality, and whether power factor meets requirements, thereby preventing losses in the power system.

04

No-Load Calibration:

Features a specially designed three-phase source output function for convenient on-site no-load calibration.

05

 

Company Qualifications

 

Wuhan Moen Intelligent Electric Co., Ltd. is situated in the Optics Valley's Wuhan East Lake High-Tech Development Zone, China's "National Independent Innovation Demonstration Zone." 8,000 square meters of buildings make up the company's 28-acre property. As a specialized business involved in the design and production of electrical equipment, it mainly supplies sophisticated high-voltage testing and detection tools to the power system's power generation, power supply, and power consumption departments as well as research facilities and power equipment manufacturers. One of the first producers in China to specialize in high-voltage testing, the company was founded in 1992 at the Wuhan High-Voltage Research Institute's High-Voltage Testing Equipment Manufacturing Plant.

 

FAQ

1)Field instrument displays voltage only, no current reading

【Symptom】After connecting current and voltage leads at the field site, the instrument displays voltage but no current reading.
【Cause】The calibrator uses a 5A clamp meter for current measurement, but the test parameter input mode is set to 5A terminal input, or configured for 100A, 500A, or 1000A clamp input modes.
【Solution】Press the "Q" key or click the " " icon to enter the test parameter settings dialog box. Click the input selection dropdown menu and correctly choose either "Clamp Meter" or 'Terminal' based on the on-site wiring configuration. If using current terminals to measure current, setting the instrument to "5A Clamp" input will also result in no current display.

2)Calibrator displays no meter error

【Cause 1】The photoelectric sensor is not properly aligned, or the pulse cable is not connected to the meter's pulse output terminals, or is incorrectly connected.
【Solution】Realign the sensor. Ensure the photoelectric sensor's pulse indicator flashes only once when the mechanical meter's black mark on the dial passes by.
Reconnect the electronic meter's pulse output terminals. Verify whether the output or ground terminals are correctly connected, or if the reactive pulse output port is accidentally engaged.
【Cause 2】During active power calibration, the actual active power on-site is very low, or the power factor is very low;
【Diagnostic Method】If the active current is too small or the active power is very low, the meter takes a long time to generate a pulse signal. Check if the total active power on the calibrator is too low.
【Solution】If the on-site current is too low, wait. If the power factor is low, implement reactive power compensation.

【Cause 3】During reactive power calibration, the actual reactive power at the site is very low, or the power factor is very high;

If reactive power is very low, the meter takes a long time to generate a pulse signal. Check if the total reactive power on the calibrator is too small.
【Solution】If the current at the site is too low, wait.

3)On-site meter calibration error exceeds tolerance or exhibits excessive fluctuation

【Symptom】During on-site meter calibration, the displayed error hovers around 3% and remains unstable, with significant variation between consecutive readings.
【Cause 1】Actual on-site current is too low (below 0.02A), falling outside the meter's guaranteed accuracy range. This causes excessive meter error.
Cause 2: Excessive harmonics at the site. When harmonics exceed 10%–60% (or even higher), calibrating certain reactive meters in such environments may yield errors exceeding 200%. Switch to fundamental or full-wave measurement modes to observe error changes and determine if a more robust meter is needed.
【Cause 3】Excessive current fluctuations at the site. When high-power impact loads are present, significant current fluctuations can disrupt the meter's energy measurement. This requires additional turns or time for the error to stabilize. If this condition persists long-term, a high-speed meter replacement is necessary.
【Cause 4】Interference from sunlight when using a photoelectric sampler to capture signals; or interference from reactive power signals when capturing photoelectric signals from electronic meters.

 

Hot Tags: three-phase meter field calibrator, China three-phase meter field calibrator manufacturers, factory, Double Clamps Digital Phase Meter, Three phase clamp on phase voltmeter, Power Quality Analyzer, Meter Calibration Test Bench, Energy Meter Field Calibrator, Three Phase Energy Meter Test Bench