Product Overview
The MOEORW-W9416B overhead line fault locator is a comprehensive testing instrument engineered for fault detection and positioning on 6 kV to 35 kV overhead power lines. It addresses multiple common line faults, including low-resistance faults, high-resistance faults, arc grounding faults and phase-to-phase short-circuit faults. This integrated device combines five core functions: fault diagnosis, AC positioning, DC positioning, AC withstand voltage test and DC withstand voltage test, forming a complete solution for overhead line fault troubleshooting and post-repair acceptance testing.
The equipment adopts innovative signal injection and detection technologies. Its AC direct connection positioning mode enables on-ground signal collection directly beneath lines without pole climbing, which greatly improves operational efficiency. For lines equipped with intelligent switches and grounding potential transformers (PT), the AC positioning mode with an external voltage booster can be applied without removing the grounding PT. The built-in high-capacity lithium battery supports portable field operation, while multi-level protection mechanisms ensure operational safety during all test procedures.
The full set consists of a transmitter, a receiver, hanging sensors, direct-connect sensors, an AC voltage booster, an arc grounding adapter and supporting accessories. It delivers stable performance for routine maintenance and emergency fault handling of overhead distribution lines.
Working Principle
Fault Diagnosis
The transmitter applies DC and AC signals to the de-energized faulty line to measure line transition resistance, AC impedance and distributed capacitance. Based on the measured electrical parameters, the system automatically analyzes fault characteristics and recommends the most applicable positioning method for subsequent operations.
AC Positioning
Two signal output configurations are available. The transmitter injects special low-frequency AC signals into the line. Current flows through the faulty line, enters the ground at the fault point and returns to the transmitter via the earth loop.
- Direct connection output: The direct-connect sensor captures composite signals of resistive current and capacitive current directly under the line. The resistive current content and total current will drop sharply after crossing the fault point, which serves as the judgment basis for fault location.
- External voltage booster output: The hanging sensor is mounted on the line pole to collect signals. By comparing current and resistive current data of three phases, operators can identify the faulty phase and determine the fault range. This mode is compatible with lines with grounding PT.
DC Positioning
The transmitter outputs 1 Hz pulsed DC signals to reproduce line faults. Pulsed DC signals are minimally affected by distributed capacitance, making this mode highly effective for high-resistance faults and arc grounding faults. The hanging sensor acquires current waveforms on the line and transmits data to the receiver via 2.4 GHz wireless communication. Continuous waveforms indicate the upstream side of the fault, while disappeared or weakened waveforms mean the downstream side of the fault. For severe arc grounding faults, the arc grounding adapter needs to be connected to stabilize signal output.
AC/DC Withstand Voltage Test
These functions are used for insulation acceptance tests after fault repair. The transmitter outputs rated AC or DC high voltage to verify the insulation performance of the restored line, with automatic discharge and over-protection functions to guarantee operator safety.
Product Configuration & Structure
Main Components
- Transmitter: The core signal generation unit, equipped with a control panel, high-voltage output socket, test ground terminal and protection ground terminal. It features an 800×480 high-brightness color LCD for parameter display and mode selection.
- Receiver: A signal receiving and analyzing unit with a built-in lithium battery and independent keyboard area. It supports data storage and waveform display, and matches with two types of sensors.
- Direct-connect Sensor: Matches the AC direct connection positioning mode for ground signal collection under lines.
- Hanging Sensor: Installed on an insulating rod and hung on overhead lines, applied to AC booster positioning and DC positioning. It supports wireless data transmission with the receiver.
- AC Voltage Booster: Raises AC output voltage to cope with high-resistance line faults.
- Arc Grounding Adapter: Used in DC positioning mode to handle arc grounding faults and avoid frequent over-current protection.
Standard Accessories
High-voltage connecting wires, grounding wires, wiring reels, insulating hanging rods, dedicated chargers for each unit and product manual.
Technical Specifications
Transmitter
|
Parameter Item |
Technical Data |
|
Working Modes |
Fault diagnosis, AC positioning, DC positioning, AC withstand voltage, DC withstand voltage |
|
Resistance Measurement Range & Accuracy |
0 ~ 600 MΩ, ±10% |
|
Capacitance Measurement Range & Accuracy |
Max 10 μF, ±20% |
|
AC Positioning (Direct Output) |
Frequency: 20 Hz off-frequency; Output current: 200 mA; Peak voltage: 560 V; Constant current with power limiting |
|
AC Positioning (External Booster) |
Frequency: 20 Hz off-frequency; Output current: 33 mA; Peak voltage: 3.4 kV; Constant current with power limiting |
|
DC Positioning |
Frequency: 1 Hz pulsed DC; Output current: 70 mA; DC voltage: 8 kV; Constant current with power limiting |
|
AC Withstand Voltage |
Max output current: 33 mA; Peak output voltage: 5 kV; Max power: 100 W |
|
DC Withstand Voltage |
Max output current: 70 mA; DC output voltage: 8 kV; Max power: 400 W |
|
Protection Functions |
Over-temperature protection, over-current protection, under-voltage shutdown, automatic discharge, 2-hour idle auto-shutdown |
|
Display |
800×480 high-brightness color LCD |
|
Built-in Battery |
480 WH lithium battery pack |
|
Charger Input & Output |
Input: AC 220 V, 50~60 Hz; Output: 54.6 V, 2 A |
|
Dimension |
450 mm × 240 mm × 270 mm |
|
Weight |
13 kg |
Receiver & Hanging Sensor
|
Parameter Item |
Technical Data |
|
Applicable Modes |
AC positioning, DC positioning |
|
Wireless Communication |
2.4 GHz, effective distance > 100 m |
|
Data Function |
Real-time data display and data memory |
|
Receiver Power Supply |
3.7 V, 6700 mAh 18650 lithium battery |
|
Hanging Sensor Power Supply |
3.7 V, 1500 mAh rechargeable lithium battery |
|
Unified Charger |
Input: AC 100~240 V, 50/60 Hz; Output: 5 V, 2 A |
|
Receiver Dimension |
226 mm × 140 mm × 55 mm |
|
Hanging Sensor Dimension |
185 mm × 140 mm × 50 mm |
|
Receiver Weight |
0.9 kg |
|
Hanging Sensor Weight |
0.5 kg |
General Operating Conditions
|
Ambient temperature |
-10 ℃ ~ 50 ℃ |
|
Relative humidity |
< 80% RH |
|
Altitude |
< 1000 m |
Main Functional Features
Integrated Multi-function Design
- This device integrates fault diagnosis, multiple positioning modes and withstand voltage test functions. It can complete fault type judgment, precise positioning and post-repair acceptance tests in one set of equipment, eliminating the need for multiple instruments and simplifying field deployment.
Diversified Positioning Modes for Full Fault Coverage
- The AC direct connection mode requires no pole climbing, which reduces labor intensity and improves inspection efficiency for low-resistance faults.
- The AC booster mode works with lines equipped with grounding PT without dismantling existing devices.
- The DC positioning mode solves difficult problems such as high-resistance faults and arc grounding faults, realizing full coverage of common overhead line faults.
Advanced Signal Processing & Accurate Judgment
- The receiver adopts fully digital high-sensitivity signal processing technology. It judges fault points by analyzing current amplitude and resistive current content (AC mode) or waveform changes (DC mode). The built-in data memory retains test data after power-off, facilitating repeated comparison and precise positioning.
Comprehensive Safety Protection System
- The transmitter is equipped with over-current, over-temperature and under-voltage protection.
- It can automatically discharge residual voltage after testing to prevent electric shock risks.
- The 2-hour idle auto-shutdown function extends battery service life and ensures safe use in unattended status.
Portable & Durable Hardware Configuration
- The transmitter is equipped with a large-capacity built-in lithium battery, supporting long-duration field operation without external power supply.
- Each component is lightweight and compact, easy to carry and transport for outdoor line maintenance.
- The high-brightness LCD ensures clear display under strong light environments.
Strong Adaptability for Complex On-site Conditions
- The AC positioning mode avoids removing grounding PT, which is suitable for widely used lines with intelligent switches.
- The matched arc grounding adapter effectively suppresses arc discharge interference and stabilizes test signals for typical arc grounding faults.
Application Scope
- Power supply enterprises: Daily maintenance, emergency troubleshooting and fault location for 6~35 kV overhead distribution lines.
- Power grid operation and maintenance departments: Regular line inspection, fault point confirmation and post-maintenance insulation acceptance tests.
- Industrial and mining enterprises: Internal self-provided overhead power line fault detection and safety testing.
- Railway, petrochemical and other industries: Fault diagnosis and positioning of special overhead power supply lines.
Routine Maintenance & Troubleshooting
Daily Maintenance
- After each use, charge all lithium batteries with the dedicated charger in a timely manner. For long-term storage, charge the whole set of equipment every six months.
- Do not charge batteries in environments below 0 ℃. The continuous charging time shall not exceed 8 hours, and special personnel shall monitor the charging process.
- Check the battery level before startup. When the remaining power is lower than 30%, complete charging prior to operation.
- Adopt intermittent working mode for the transmitter to avoid long-time continuous operation, so as to extend the service life of the device.
- Keep all sensors and connecting wires clean and intact, and avoid violent pulling or extrusion.
Common Fault Troubleshooting
- Device fails to power on: The battery is fully depleted. Connect the dedicated charger for charging and retry.
- Automatic shutdown during operation: It is caused by low battery voltage or 2-hour idle auto-shutdown. Recharge the battery or restart the device.
- Immediate shutdown after power-on: The battery voltage is too low. Perform full charging before use.
- Unable to start high-voltage output: Check whether the protection ground and test ground are reliably connected to the ground grid. Reconnect the grounding wires if the grounding resistance is excessive.
- Poor wireless communication between receiver and hanging sensor: Adjust the distance between the two devices (keep between 2 m and 100 m), and confirm that the sensor is powered on normally.
Warranty Policy
- The whole device enjoys a 3-year warranty. The built-in lithium battery is warranted for 1 year.
- For failures caused by improper use or faults occurring beyond the warranty period, the company provides maintenance services and only charges for component costs.
- Do not disassemble the device privately for unknown faults. Contact the manufacturer for professional maintenance.
FAQ
Q: Is it necessary to cut off the line power before testing?
A: Yes. All tests must be performed on de-energized overhead lines. Cut off the line switch completely before wiring.
Q: Can the AC positioning mode be used for lines with grounding PT?
A: Yes. Both AC direct connection mode and AC booster mode can work normally without removing the grounding PT.
Q: Which mode is selected for arc grounding faults?
A: Choose DC positioning mode and connect the supporting arc grounding adapter. If the line has grounding PT, remove the PT first.
Q: Why does the current value drop sharply during AC positioning?
A: It indicates that the detection position has passed the fault point, and you can locate the fault section by segmented measurement.
Q: What is the purpose of AC/DC withstand voltage functions?
A: They are used for insulation performance acceptance tests after line fault repair to verify whether the line restores normal operating conditions.
Q: What is the maximum continuous working time of the transmitter?
A: The normal continuous working time exceeds 8 hours, and about 4 hours under extreme working conditions.
Hot Tags: single-phase ground fault locator for distribution lines, China single-phase ground fault locator for distribution lines manufacturers, factory, Cable And Pipe Locator, Cable Fault Location Detector, intelligent cable identifier, Line Parameter Tester, On site Multi parameter Tester for Coiled Cable, Overhead Line Fault Location Instrument